PROFINET IO protocol
vacon • 17
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
5
5.3
PROFINET IO process communication
The PROFIdrive profile specifies telegrams used for process communication. The VACON
®
100 AC
drive supports four types of different telegrams with and without extra process data items. These
telegrams contain either PROFIdrive or VACON
®
specific signals or a combination of both.
The following chapters describe the different types of telegrams and the signals that form them.
5.3.1
Telegram types
The telegrams defined in the chapters below use different combinations of control and reference
values. Control and status word can be either
VACON
®
specific or defined in PROFIDrive standard.
Speed reference and actual values can use different scaling.
Please check details of telegrams before taking them in use.
5.3.1.1
Standard Telegram 1 and variants
Standard Telegram 1 types are used, when a standard VACON
®
application is used and PROFIdrive
functionality is required. These telegrams (table below) use PROFIdrive-defined control word,
status word, speed setpoint value and speed actual value. When using these telegrams, the process
data fields are communicated as 16-bit values. STW1 will force edge sensitive run control.
Table 8. Standard Telegram 1 and variants
Telegram No.
Telegram
Abbreviation
1
Standard Telegram 1
ST1
102
Standard Telegram 1 + 1 Process Data
ST1 + 1 PD
103
Standard Telegram 1 + 2 Process Data
ST1 + 2 PD
104
Standard Telegram 1 + 3 Process Data
ST1 + 3 PD
100
Standard Telegram 1 + 4 Process Data
ST1 + 4 PD
105
Standard Telegram 1 + 5 Process Data
ST1 + 5 PD
106
Standard Telegram 1 + 6 Process Data
ST1 + 6 PD
107
Standard Telegram 1 + 7 Process Data
ST1 + 7 PD
101
Standard Telegram 1 + 8 Process Data
ST1 + 8 PD
Table 9. Standard Telegram 1 setpoint and actual data
Bytes
Setpoint
Actual value
1...2
STW1
5.3.2.1
ZSW1
5.3.2.2
3...4
NSOLL_A
5.3.2.3
NIST_A
5.3.2.4
5...6
PDI1
5.3.2.11
PDO1
5.3.2.11
7...8
PDI2
PDO2
...
...
...
19...20
PDI8
PDO8