Instruction  

SONOMETER™ 1100

The push-button is used to switch through the various displays. 
The button can be pressed for a short or long time. A short press 
of the button 
(< 3 seconds) switches to the next display within a loop and a long 
press (> 3 seconds) switches to the next display loop. The “Energy” 
window (sequence 1.1) in the main loop is the basic display. The 
meter automatically switches off the display to save power if the 
button is not pressed for 
approx. 4 minutes (except in the event of fault) and returns to the 
basic display when the button is pressed again.

10.0    Simple operation

The error code is displayed in the main loop if an error occurs. All the 
other windows can still be selected by pressing the button. The error 
code display appears again automatically if the button is not pressed 
for approx. 4 minutes.

The error display disappears automatically as soon as the cause of the 
error has been cleared. All errors present longer than 6 minutes are 
saved in the error log.

Error 
code

Description

C – 1

Basic parameters saved in flash or RAM have been lost

E 1

Temperature range outside [-19.9 °C ... 199.9 °C] e.g.

sensor short-circuit, sensor break

E 3**

Flow and return sensors interchanged

E 4

Hardware error US measurement, e.g. transducer

or control defective or short circuit

E 5

Communication not possible (to many frequent 

readouts)

E 6**

Flow direction of flow meter incorrect

E 7

No plausible ultrasound receiver signal, e.g. air in the
measuring path

E 8

No primary power supply (only with power supply 
unit); supply via backup battery

E 9

Battery nearly discharged, end of lifetime reached

E A*

Leak: Pipe break detection

E b*

Leak: Energy meter leak detection

E C*

Leak: Leak pulse input 1

E d*

Leak: Leak pulse input 2

* optional ** application dependent

11.0    Error codes

Danfoss District Energy 

 

 

 

 

VI.SH.K1.02 

 

 

 

               DEN-SMT/PL

9

Summary of Contents for SONOMETER 1100

Page 1: ...Sheet FW510 If water additives are used e g corrosion protection the user must make sure that the corrosion resistance is adequate The specified medium temperature is 5 90 C 105 C 130 C 150 C The tem...

Page 2: ...low sensor in a tilted 45 position The minimum system pressure must be 1 bar to avoid cavitation Make sure the energy meter is installed sufficiently far away from possible sources of electromagnetic...

Page 3: ...be inserted as far as the bottom of the pocket and then secured The pockets are best installed inT pieces with a 45 or 90 angle The tip of the pocket must point in the opposite direction to the direct...

Page 4: ...on pressing button and the date and time are still updated but none of the measuring functions work incl the flow rate measurement Communication still functions over the optional M Bus RS485 and RS23...

Page 5: ...e formed ribbon cable at both ends 3 Close the lid and check the meter for correct operation by pressing the push button loop 3 Renew the seal of the housing lid if the meter functions correctly The r...

Page 6: ...tandard and is encrypted Reading modes Walk By Drive By Fixed Network For problematic radio installations shield the external radio module set can also be used 8 2 M Bus communication module The M Bus...

Page 7: ...nd can be used as the supply for a flow sensor The pulse output has the same characteristics as pulse output 1 speci fied under 8 6 It is not however electrically isolated 8 8 Analogue output function...

Page 8: ...Future accounting date 1 2 3 Accounting date 1 previous year Accounting date 1 previous year energy Accd 1L 2 4 Accounting date 2 Accounting date 2 energy Accd 2A 2 5 Accd 2 Future accounting date 2...

Page 9: ...prox 4 minutes The error display disappears automatically as soon as the cause of the error has been cleared All errors present longer than 6 minutes are saved in the error log Error code Description...

Page 10: ...Instruction SONOMETER 1100 VI SH K1 02 Produced by Danfoss A S 12 2014...

Reviews: