background image

Instruction  

SONOMETER™ 1100

DEN-SMT/PL 

 

 

 

 

 

VI.SH.K1.02 

 

 

               Danfoss District Enrgy

2

Depending on the application (heat or cooling meter), the energy 
meter is installed in the forward or return pipe of the system. The 
installation location is printed on the meter and is also visible in the 
information loop in the calculator menu. The flow sensor must be 
installed so that the direction of flow corresponds to the direction 
of the arrow on the sensor. Calming sections are not needed before 
or after the energy meter, but calming sections of 3xDN are recom-
mended before the meter.
The energy meter can be installed in both horizontal and vertical pipe 
sections, but every time so that air bubbles cannot collect in the meter. 
The flow sensor must always be filled with water. Avoid frost on the 
meter.
We recommend installing the flow sensor in a tilted (45°) position. 
The minimum system pressure must be 1 bar to avoid cavitation.

Make sure the energy meter is installed sufficiently far away from 
possible sources of electromagnetic interference (switches, electric 
motors, fluorescent lamps, etc...)

.

To simplify the removal of the energy meter it is recommended to 
install isolating valves before and after the meter.
The energy meter should be installed in an accessible position for 
service and operating personnel.
Initial operation is to be carried out and recorded after installation.

For medium temperatures of more than 90°C or if T

water

 < T

ambient

 

(for application as cooling meter or heat meter with cooling tariff), 
the calculator must be removed from the meter and installed 
a sufficient distance away from heat sources.
A wall holder (supplied with meter) or a space holder (optional) is 
available for this purpose.

3.0  Installation of energy meter

T: 5 ... 90

°

T

water

 > T

ambient

T: 5 ... 130 / 150

°

T

water

 < T

ambient

space holder

wall mounting

Summary of Contents for SONOMETER 1100

Page 1: ...Sheet FW510 If water additives are used e g corrosion protection the user must make sure that the corrosion resistance is adequate The specified medium temperature is 5 90 C 105 C 130 C 150 C The tem...

Page 2: ...low sensor in a tilted 45 position The minimum system pressure must be 1 bar to avoid cavitation Make sure the energy meter is installed sufficiently far away from possible sources of electromagnetic...

Page 3: ...be inserted as far as the bottom of the pocket and then secured The pockets are best installed inT pieces with a 45 or 90 angle The tip of the pocket must point in the opposite direction to the direct...

Page 4: ...on pressing button and the date and time are still updated but none of the measuring functions work incl the flow rate measurement Communication still functions over the optional M Bus RS485 and RS23...

Page 5: ...e formed ribbon cable at both ends 3 Close the lid and check the meter for correct operation by pressing the push button loop 3 Renew the seal of the housing lid if the meter functions correctly The r...

Page 6: ...tandard and is encrypted Reading modes Walk By Drive By Fixed Network For problematic radio installations shield the external radio module set can also be used 8 2 M Bus communication module The M Bus...

Page 7: ...nd can be used as the supply for a flow sensor The pulse output has the same characteristics as pulse output 1 speci fied under 8 6 It is not however electrically isolated 8 8 Analogue output function...

Page 8: ...Future accounting date 1 2 3 Accounting date 1 previous year Accounting date 1 previous year energy Accd 1L 2 4 Accounting date 2 Accounting date 2 energy Accd 2A 2 5 Accd 2 Future accounting date 2...

Page 9: ...prox 4 minutes The error display disappears automatically as soon as the cause of the error has been cleared All errors present longer than 6 minutes are saved in the error log Error code Description...

Page 10: ...Instruction SONOMETER 1100 VI SH K1 02 Produced by Danfoss A S 12 2014...

Reviews: