8.0 Communication

The calculator supports three communication channels. Additional 
to the radio communication two wired communication modules can 
be used, e.g. two M-Bus modules. The protocol of the two channels 
can be different but is preset at factory, whereby the radio telegram 
will have the same content than the module 2. Customer specific 
requirements can be defined by using the IZAR@SET Software. Each 
port has its own primary address. Both ports have a common second-
ary address, which is set to the serial number ex works.

8.1   Communication via radio

The integrated radio module is an interface for communication with 
OMS radio receivers.
Unidirectional communication has the following specification:
•  The module sends every 12 s (send period 0.1 % of duty 

cycle (min. 8 s); variable, depending on protocol length and 
programming)

•  The radio communicates the actual data register
•  Transmission frequency: 868 MHz or 434 MHz
•  Various Diehl Metering receivers are available for receiving 

the protocol (e.g. Bluetooth, GPRS, LAN, …)

•  The protocol corresponds to the”Open Metering” 

or “DM Standard” and is encrypted

•  Reading modes: Walk-By, Drive-By, Fixed-Network
•  For problematic radio installations (shield) the external radio 

module set can also be used 

8.2   M-Bus communication module

The M-Bus communication module is a serial interface for communi-
cation with external devices (M-Bus control centres), e.g. IZAR CENT-
ER. A number of meters can be connected to a control centre. The 
module contains a 2-pole terminal strip with terminals marked 24, 25.
•  The connection is not polarity-conscious 

and is electrically isolated

•  M-Bus protocol to EN 1434 standard;
•  300 or 2400 baud (auto baud detect)
•  Connection for 2 x 2.5 mm² wires
•  Current drawn: one M-Bus load

8.3   RS232 Communication module

The RS232 communication module is a serial interface for communi-
cating with external devices, e.g. PC; 300 or 2400 bauds. The module 
contains a 3-pole terminal strip with terminals marked 62 (Dat), 63 
(Req) and 64 (GND). The used communication protocol is M-Bus.

The coloured wires are to be connected as shown:

8.4   RS485 Communication module

The RS485 communication module is a serial interface for commu-
nication with external devices, e.g. PC; 2400 bauds only. The used 
communication protocol is M-Bus.
The module contains a 4-pole terminal strip with terminals marked 
D+, D-, +12 V and GND. The module needs an external power supply 
of 12 VDC ±5 V.

                                                     

                                                    

                   

                                

62 = brown
63 = white
64 = green

Summary of Contents for SONOMETER 1100

Page 1: ...Sheet FW510 If water additives are used e g corrosion protection the user must make sure that the corrosion resistance is adequate The specified medium temperature is 5 90 C 105 C 130 C 150 C The tem...

Page 2: ...low sensor in a tilted 45 position The minimum system pressure must be 1 bar to avoid cavitation Make sure the energy meter is installed sufficiently far away from possible sources of electromagnetic...

Page 3: ...be inserted as far as the bottom of the pocket and then secured The pockets are best installed inT pieces with a 45 or 90 angle The tip of the pocket must point in the opposite direction to the direct...

Page 4: ...on pressing button and the date and time are still updated but none of the measuring functions work incl the flow rate measurement Communication still functions over the optional M Bus RS485 and RS23...

Page 5: ...e formed ribbon cable at both ends 3 Close the lid and check the meter for correct operation by pressing the push button loop 3 Renew the seal of the housing lid if the meter functions correctly The r...

Page 6: ...tandard and is encrypted Reading modes Walk By Drive By Fixed Network For problematic radio installations shield the external radio module set can also be used 8 2 M Bus communication module The M Bus...

Page 7: ...nd can be used as the supply for a flow sensor The pulse output has the same characteristics as pulse output 1 speci fied under 8 6 It is not however electrically isolated 8 8 Analogue output function...

Page 8: ...Future accounting date 1 2 3 Accounting date 1 previous year Accounting date 1 previous year energy Accd 1L 2 4 Accounting date 2 Accounting date 2 energy Accd 2A 2 5 Accd 2 Future accounting date 2...

Page 9: ...prox 4 minutes The error display disappears automatically as soon as the cause of the error has been cleared All errors present longer than 6 minutes are saved in the error log Error code Description...

Page 10: ...Instruction SONOMETER 1100 VI SH K1 02 Produced by Danfoss A S 12 2014...

Reviews: