Instruction  

SONOMETER™ 1100

Handle the temperature sensors carefully!
The sensor cables are fitted with coloured type labels:

Red (TH): sensor in hot line, 
Blue (TC): sensor in cold line

Make sure the sensors are mounted symmetrically (both directly 
immersed, or both installed in a pocket). The maximum cable length 
is 10 m. The connecting cables must not be shortened or extended. 
For DN 15 and DN 20, the sensors must be directly immersed.
The free temperature sensor can be installed in a ball valve /adapter 
or in a conformity tested pocket for this type of sensor. Ensure that the 
temperature sensors are permanently connected during operation.

For installation in a ball valve (same for adapter), a 4-piece coupling 
set is enclosed in a separate bag. See procedure under item 1…5 
on the right. Insert an O-ring in the sensor hole using the mounting 
pin supplied.
If the sensor is installed in a pocket, it must be inserted as far as the 
bottom of the pocket and then secured. The pockets are best installed 
in T-pieces with a 45° or 90° angle. The tip of the pocket must point in 
the opposite direction to the direction of flow and must be located 
in the middle of the pipe.
The temperature sensors must be sealed after installation in the 
pockets.

Connect the sensor cables to terminals 5-6 / 7-8 as shown in the  
table below.

Meter type

Sensor 

marking

Terminal

Installation 

position

Heat meter

Red

T

Hot

 (5,6)

Inlet

Blue

T

Cold

 (7, 8)

Outlet

Heat meter with 
cooling tariff

Red

T

Hot

 (5, 6)

Inlet

Blue

T

Cold

 (7, 8)

Outlet

Cooling meter

Red

T

Hot

 (5, 6)

Outlet

Blue

T

Cold

 (7, 8)

Inlet

Cable entries:
1: Cable entry for connecting T

Hot

 (5,6)

2: Cable entry for connecting T

Cold

 (7,8)

                    

Terminals for temperature sensors:

                  

4.0  Installation of temperature sensors

 

The operation of any violation of this guidance will result in 
immediate invalidation of the factory warranty and verification.

Tighten the plug screw with a torque of approx. 12 Nm

Installation in a ball valve:

Installation in a pocket:

Danfoss District Energy 

 

 

 

 

VI.SH.K1.02 

 

 

 

               DEN-SMT/PL

3

Summary of Contents for SONOMETER 1100

Page 1: ...Sheet FW510 If water additives are used e g corrosion protection the user must make sure that the corrosion resistance is adequate The specified medium temperature is 5 90 C 105 C 130 C 150 C The tem...

Page 2: ...low sensor in a tilted 45 position The minimum system pressure must be 1 bar to avoid cavitation Make sure the energy meter is installed sufficiently far away from possible sources of electromagnetic...

Page 3: ...be inserted as far as the bottom of the pocket and then secured The pockets are best installed inT pieces with a 45 or 90 angle The tip of the pocket must point in the opposite direction to the direct...

Page 4: ...on pressing button and the date and time are still updated but none of the measuring functions work incl the flow rate measurement Communication still functions over the optional M Bus RS485 and RS23...

Page 5: ...e formed ribbon cable at both ends 3 Close the lid and check the meter for correct operation by pressing the push button loop 3 Renew the seal of the housing lid if the meter functions correctly The r...

Page 6: ...tandard and is encrypted Reading modes Walk By Drive By Fixed Network For problematic radio installations shield the external radio module set can also be used 8 2 M Bus communication module The M Bus...

Page 7: ...nd can be used as the supply for a flow sensor The pulse output has the same characteristics as pulse output 1 speci fied under 8 6 It is not however electrically isolated 8 8 Analogue output function...

Page 8: ...Future accounting date 1 2 3 Accounting date 1 previous year Accounting date 1 previous year energy Accd 1L 2 4 Accounting date 2 Accounting date 2 energy Accd 2A 2 5 Accd 2 Future accounting date 2...

Page 9: ...prox 4 minutes The error display disappears automatically as soon as the cause of the error has been cleared All errors present longer than 6 minutes are saved in the error log Error code Description...

Page 10: ...Instruction SONOMETER 1100 VI SH K1 02 Produced by Danfoss A S 12 2014...

Reviews: