background image

Danfoss District Energy 

 

 

 

 

VI.SH.K1.02 

 

 

 

               DEN-SMT/PL

1

Instruction

1.0   Table of contents

SONOMETER™ 1100

Ultrasonic compact energy meter

2.0  Safety notes and product information

1.0  

Table of contents

 .........................................................................................................................................................................................................................................................................

1

2.0  

Safety notes and product information

 ........................................................................................................................................................................................................................

1

3.0  

Installation of energy meter

 ................................................................................................................................................................................................................................................

2

4.0  

Installation of temperature sensors

 ...............................................................................................................................................................................................................................

3

5.0  

Power  supply

 ..................................................................................................................................................................................................................................................................................

4

6.0  

Start-up  operation

 ......................................................................................................................................................................................................................................................................

5

7.0  

Expansion  modules

 ...................................................................................................................................................................................................................................................................

5

8.0  

Communication

 ...........................................................................................................................................................................................................................................................................

6

9.0  

Display

 .................................................................................................................................................................................................................................................................................................

8

10.0  Simple operation

 .........................................................................................................................................................................................................................................................................

9

11.0  Error codes

 .......................................................................................................................................................................................................................................................................................

9

 

Following instructions refer to the ultrasonic energy meter.

The regulations on the use of energy meters must be observed! The 
meter installation is only to be performed by an installation and/
or electrical contractor using personnel trained in the installation 
and use of electrical equipment and familiar with the Low Voltage 
Directive.

- Medium: water, as per AGFW Instruction Sheet FW510.If water 

additives are used (e.g. corrosion protection), the user must 
make sure that the corrosion resistance is adequate.

- The specified medium temperature 

is 5 ... 90°C/105°C/130°C(150°C)

- The temperature range depends on variant and nominal size
- The exact temperature range is shown on the type plate
- The encapsulated variant is to be used if condensation is 

expected

- The specified operating/ambient conditions are: 

5…55 °C; max. 93% rel. humidity

- Protection class: calculator IP54; flow sensor 

IP54 (heating)/IP65 (cooling, heat/cooling)

- Ambient temperatures below 35 °C ensures typical battery 

lifetime

This installation guide is intended for trained personnel and 
does not contain any basic working steps.

If the flow sensor is insulated with the pipeline, 
the calculator must be accessible.

Safety Note

The seal on the energy meter must not be damaged! 
A damaged seal will result in immediate invalidation of the 
factory warranty and verification. The cables supplied with the 
meter must not be shortened, extended or changed in any 
other way.

Summary of Contents for SONOMETER 1100

Page 1: ...Sheet FW510 If water additives are used e g corrosion protection the user must make sure that the corrosion resistance is adequate The specified medium temperature is 5 90 C 105 C 130 C 150 C The tem...

Page 2: ...low sensor in a tilted 45 position The minimum system pressure must be 1 bar to avoid cavitation Make sure the energy meter is installed sufficiently far away from possible sources of electromagnetic...

Page 3: ...be inserted as far as the bottom of the pocket and then secured The pockets are best installed inT pieces with a 45 or 90 angle The tip of the pocket must point in the opposite direction to the direct...

Page 4: ...on pressing button and the date and time are still updated but none of the measuring functions work incl the flow rate measurement Communication still functions over the optional M Bus RS485 and RS23...

Page 5: ...e formed ribbon cable at both ends 3 Close the lid and check the meter for correct operation by pressing the push button loop 3 Renew the seal of the housing lid if the meter functions correctly The r...

Page 6: ...tandard and is encrypted Reading modes Walk By Drive By Fixed Network For problematic radio installations shield the external radio module set can also be used 8 2 M Bus communication module The M Bus...

Page 7: ...nd can be used as the supply for a flow sensor The pulse output has the same characteristics as pulse output 1 speci fied under 8 6 It is not however electrically isolated 8 8 Analogue output function...

Page 8: ...Future accounting date 1 2 3 Accounting date 1 previous year Accounting date 1 previous year energy Accd 1L 2 4 Accounting date 2 Accounting date 2 energy Accd 2A 2 5 Accd 2 Future accounting date 2...

Page 9: ...prox 4 minutes The error display disappears automatically as soon as the cause of the error has been cleared All errors present longer than 6 minutes are saved in the error log Error code Description...

Page 10: ...Instruction SONOMETER 1100 VI SH K1 02 Produced by Danfoss A S 12 2014...

Reviews: