© Danfoss | 2017.05 | 3

VI.LY.A1.

3A

/VI.C6.F3.3A 

Thermostatic actuator QT / QTL

ENGLISH

Assembly 

Insert adapter 

 into thermostat neck

Design 

Mount AB‑QM valve 

 on hot‑water pipe (see 

instruction for AB‑QM)

Setting knob 

Adapter

AB‑QM valve

Hot‑water pipe

Temperature sensor

Set desired setting on AB‑QM 
(see instruction for AB‑QM)

Mounting 

QT/QTL should be mounted on the AB‑QM by 
hand. Maximum allowed torque is 5 Nm.

Sensor installation 

AB‑QM is to be installed on the return pipe. 
In general the sensor must always be placed 
warmer than the thermostat head.

In case of one‑pipe system the AB‑QM needs to 
be installed after and as close as possible to the 
last radiator.

QT should be mounted on the AB‑QM by hand. 
Maximum allowed torque is 5 Nm.

For proper heat transfer between a heating 
water pipe and the thermostat sensor, it is very 
important to apply thermo paste (included in 
the box) on the surfaces in contact.

It is recommended to insulate the sensor if 
the thermostat is installed in a very cold place 
(< 5 °C).

Sensor itself can be mounted in any direction. It 
can be mounted above or below sensor head.

Setting 

QT/QTL temperature setting depends on AB‑QM 
flow setting.

It is necessary to set the AB‑QM to desired 
setting before the thermostat is mounted. It is 
recommended to set AB‑QM between 30 and 
70 % flow setting.

QT/QTL thermostat is set to the desired setting 
by hand. When minimum or maximum setting 
is required, QT/QTL setting knob is to be moved 
slightly in opposite direction to ensure optimal 
performance of the thermostat.

Please note that the attached tables are indicative and will 
vary depending on the application. They are to be used as a 
guidance only. For exact temperature verification tempera‑
ture needs to be measured at reference point and the sensor 
setting adjusted accordingly.

AB‑QM DN 10‑20 (35‑50 °C)

Temp. 

 setting

(°C)

QT Sensor setting (turns)

0

1

2

3

4

5

6

A

B

‑Q

M (

fl

ow s

et

ti

n

g)

20 % 38.0 40.5 43.0 45.5 48.0 50.5 53.0
30 % 37.0 39.5 42.0 44.5 47.0 49.5 52.0
40 % 36.0 38.5 41.0 43.5 46.0 48.5 51.0
50 % 35.0 37.5 40.0 42.5 45.0 47.5 50.0
60 % 34.0 36.5 39.0 41.5 44.0 46.5 49.0
70 % 33.0 35.5 38.0 40.5 43.0 45.5 48.0
80 % 32.0 34.5 37.0 39.5 42.0 44.5 47.0
90 % 31.0 33.5 36.0 38.5 41.0 43.5 46.0

100 % 30.0 32.5 35.0 37.5 40.0 42.5 45.0

Factory setting of the thermostat is 4.

AB‑QM DN 25‑32 (35‑50 °C)

Temp. 

 setting

(°C)

QT Sensor setting (turns)

0

1

2

3

4

5

6

A

B

‑Q

M (

fl

ow s

et

ti

n

g)

20 % 39.5 42.0 44.5 47.0 49.5 52.0 54.5
30 % 38.0 40.5 43.0 45.5 48.0 50.5 53.0
40 % 36.5 39.0 41.5 44.0 46.5 49.0 51.5
50 % 35.0 37.5 40.0 42.5 45.0 47.5 50.0
60 % 33.5 36.0 38.5 41.0 43.5 46.0 48.5
70 % 32.0 34.5 37.0 39.5 42.0 44.5 47.0
80 % 30.5 33.0 35.5 38.0 40.5 43.0 45.5
90 % 29.0 31.5 34.0 36.5 39.0 41.5 44.0

100 % 27.5 30.0 32.5 35.0 37.5 40.0 42.5

Factory setting of the thermostat is 4.

AB‑QM DN 10‑20 (45‑60 °C)

Temp. 

 setting

(°C)

QT Sensor setting (turns)

0

1

2

3

4

5

6

A

B

‑Q

M (

fl

ow s

et

ti

n

g)

20 % 48.0 50.5 53.0 55.5 58.0 60.5 63.0
30 % 47.0 49.5 52.0 54.5 57.0 59.5 62.0
40 % 46.0 48.5 51.0 53.5 56.0 58.5 61.0
50 % 45.0 47.5 50.0 52.5 55.0 57.5 60.0
60 % 44.0 46.5 49.0 51.5 54.0 56.5 59.0
70 % 43.0 45.5 48.0 50.5 53.0 55.5 58.0
80 % 42.0 44.5 47.0 49.5 52.0 54.5 57.0
90 % 41.0 43.5 46.0 48.5 51.0 53.5 56.0

100 % 40.0 42.5 45.0 47.5 50.0 52.5 55.0

Factory setting of the thermostat is 4.

AB‑QM DN 25‑32 (45‑60 °C)

Temp. 

 setting

(°C)

QT Sensor setting (turns)

0

1

2

3

4

5

6

A

B

‑Q

M (

fl

ow s

et

ti

n

g)

20 % 49.5 52.0 54.5 57.0 59.5 62.0 64.5
30 % 48.0 50.5 53.0 55.5 58.0 60.5 63.0
40 % 46.5 49.0 51.5 54.0 56.5 59.0 61.5
50 % 45.0 47.5 50.0 52.5 55.0 57.5 60.0
60 % 43.5 46.0 48.5 51.0 53.5 56.0 58.5
70 % 42.0 44.5 47.0 49.5 52.0 54.5 57.0
80 % 40.5 43.0 45.5 48.0 50.5 53.0 55.5
90 % 39.0 41.5 44.0 46.5 49.0 51.5 54.0

100 % 37.5 40.0 42.5 45.0 47.5 50.0 52.5

Factory setting of the thermostat is 4.

Disposal instruction

This product should be dismantled 
and its components sorted, if possible, 
in various groups before recycling or 
disposal. 

Always follow the local disposal regulations.

Summary of Contents for QT

Page 1: ...ll t m www danfoss com 5 oldal POLSKI Element termostatyczny QT QTL www heating danfoss pl Strona 6 QT QTL www danfoss ru 7 QT QTL www danfoss com cn 8 ESKY Termostatick pohon QT QTL www cz danfoss co...

Page 2: ...2 Danfoss 2017 05 VI LY A1 3A VI C6 F3 3A Thermostatic actuator QT QTL Best performance Thermo paste Sensor holder Fastener Hot water supply...

Page 3: ...etting turns 0 1 2 3 4 5 6 AB QM flow setting 20 38 0 40 5 43 0 45 5 48 0 50 5 53 0 30 37 0 39 5 42 0 44 5 47 0 49 5 52 0 40 36 0 38 5 41 0 43 5 46 0 48 5 51 0 50 35 0 37 5 40 0 42 5 45 0 47 5 50 0 60...

Page 4: ...ierungshilfe gedacht Zur exakten Bestimmung muss die Temperatur am Referenzpunkt gemes sen und die F hler Einstellung entsprechend angepasst werden AB QM DN 10 20 35 50 C Temp einstellung C QT Handrad...

Page 5: ...DN 10 20 35 50 C H m rs klet be ll t s C QT rz kel be ll t s fordulat 0 1 2 3 4 5 6 T rfogat ram be ll t s 20 38 0 40 5 43 0 45 5 48 0 50 5 53 0 30 37 0 39 5 42 0 44 5 47 0 49 5 52 0 40 36 0 38 5 41...

Page 6: ...i temperatury zmierzy j w punkcie odniesienia i odpowiednio wyregulowa czujnik AB QM DN 10 20 35 50 C Nastawa temperatury C QT nastawa termostatu obroty 0 1 2 3 4 5 6 AB QM nastawa przep ywu 20 38 0 4...

Page 7: ...5 40 0 42 5 45 0 47 5 50 0 60 33 5 36 0 38 5 41 0 43 5 46 0 48 5 70 32 0 34 5 37 0 39 5 42 0 44 5 47 0 80 30 5 33 0 35 5 38 0 40 5 43 0 45 5 90 29 0 31 5 34 0 36 5 39 0 41 5 44 0 100 27 5 30 0 32 5 35...

Page 8: ...51 5 50 35 0 37 5 40 0 42 5 45 0 47 5 50 0 60 33 5 36 0 38 5 41 0 43 5 46 0 48 5 70 32 0 34 5 37 0 39 5 42 0 44 5 47 0 80 30 5 33 0 35 5 38 0 40 5 43 0 45 5 90 29 0 31 5 34 0 36 5 39 0 41 5 44 0 100 2...

Page 9: ...ven teploty C Nastaven idla QT stupn oto en 0 1 2 3 4 5 6 Ventil AB QM nastaven pr toku 20 38 0 40 5 43 0 45 5 48 0 50 5 53 0 30 37 0 39 5 42 0 44 5 47 0 49 5 52 0 40 36 0 38 5 41 0 43 5 46 0 48 5 51...

Page 10: ...stada AB QM DN 10 20 35 50 C Temp seade C QT anduri seade p ret 0 1 2 3 4 5 6 AB QM vooluhulga seade 20 38 0 40 5 43 0 45 5 48 0 50 5 53 0 30 37 0 39 5 42 0 44 5 47 0 49 5 52 0 40 36 0 38 5 41 0 43 5...

Page 11: ...tatyti jutikl AB QM DN 10 20 35 50 C Temp nustatymas C QT jutiklio nustatymas pasukimai 0 1 2 3 4 5 6 AB QM flow setting 20 38 0 40 5 43 0 45 5 48 0 50 5 53 0 30 37 0 39 5 42 0 44 5 47 0 49 5 52 0 40...

Page 12: ...rb bu emiet v r ka pievienot s tabulas ir informat vas un var at irties atkar b no pielietojuma T s var izmantot tikai k vadl niju Prec zai temperat ras verifik cijai temperat ru ir j m ra atskaites p...

Reviews: