Name of directive
Number/Description
EMC Directive (2014/30/EU)
EN 50011
EN 61000-6-3
EN 61800-3
Low Voltage Directive (2014/35/EC)
EN 50178
EN 61800-5-1
Table 26: Safety Standards
Name of standard
Number/description
Safety of Machinery
EN ISO 13849-1
IEC 62061
IEC 60204-1
Functional Safety
IEC 61508-1 to -7
IEC 61800-5-2
IEC 61784-3
Table 27: Safety Function
IEC 61800-5-2
IEC 60204-1
Safe Torque Off (STO)
Stop Category 0
NOTICE
The data in
responsible for calculating the total safety metrics/values of the system.
Table 28: Safety Performance
Name of performance
Type/description
Safety Integrity Level
SIL 2
SIL CL2
HFT (IEC 61508)
Hardware Fault Tolerance = 1
Subsystem classification
Type B
Probability of dangerous failure per hour
PFH: 1,52 e-8
Probability of dangerous failure on demand
PFD: 1,33 e-3
Category
Cat 3
Performance level
PL d (cat 3)
Specifications
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578
74 | Danfoss A/S © 2020.02