Procedure
1. In MCT 10, establish a connection between the PC and the drive.
2. In MCT 10, select the
Safe Plug-in
.
e3
0b
e0
71
.1
1
3. Select
PROFIsafe
in
Safe input
⇒
Telegram Selection
and enter the destination address in the
Destination Address
field.
e3
0b
e0
78
.1
1
4. Select the appropriate safe function for digital input 1 in the DI1 group.
e3
0b
e0
79
.1
1
5. Make the other application-specific settings.
6. In the
Safe Plug-in
, click
Write to Drive
.
7. If the safety option is in blank initial state, it prompts for a new password.
A In the
New password
dialog box, enter the current password (which is the default password - 12345678) and the new password
- then click
OK
.
Commissioning
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578| 29
Danfoss A/S © 2020.02