5 Commissioning
5.1 Before Commissioning
When commissioing/recommissioning:
•
Secure the site in accordance with regulations (barrier, warnings, signs, and more). Only qualified personnel is allowed to
commission/recommission the system.
•
Refer to the guidelines, information, and specifications stated in the operating guide of the relevant programmable control system.
•
Make sure that no personal injury and/or material damage can occur, even if the plant/machine moves unintentionally.
CAUTION
ELECTROSTATIC DISCHARGE
Electrostatic discharge can damage components.
-
Ensure discharge before touching the safety option, for example by touching a grounded, conductive surface or by wearing
a grounded armband.
WARNING
RISK OF ELECTROCUTION
Wiring the electrical connections on the drive while voltage is applied can lead to death or serious injury.
-
Switch off power.
-
Make sure that the control cabinet is provided with an access lock or warning signs.
-
DO NOT switch on voltage until the system is commissioned.
Refer to the VLT® AutomationDrive FC 301/FC 302 Operating Guide or the VLT® Decentral Drive FCD 302 Operating Guide for further
information on the drive. Refer to the VLT® Motion Control Tool MCT 10 Operating Guide for further information on the Safe Plug-in.
5.2 Commissioning Procedure
Prerequisites:
The following components are required to perform the necessary steps for commissioning the safety option:
•
Installation of MCT 10 Set-up Software version 4.40 or later.
•
A connection between the PC and the control card of the drive.
NOTICE
If RS485 is used, set the protocol for serial communication to
[0] FC-MC
in
parameter 8-30 Protocol
(only accessible through the
LCP).
Commissioning
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578| 27
Danfoss A/S © 2020.02