Bit 15, Safe function pending
•
Bit 15 = 0, No safe function is pending.
•
Bit 15 = 1, A safe function is pending.
Bit 16, General reset
•
Bit 16 = 0, No change in state.
•
Bit 16 = 1, A general reset is done.
Bit 17, Customization confirmed
•
Bit 17 = 0, No change in state.
•
Bit 17 = 1, Customization confirmed.
Bit 18, Customization aborted
•
Bit 18 = 0, No change in state.
•
Bit 18 = 1, Customization aborted.
Bit 19, Customization requested
•
Bit 19 = 0, No change in state.
•
Bit 19 = 1, Customization requested.
Bit 20, Suspension of speed monitoring
•
Bit 20 = 0, No change in state.
•
Bit 20 = 1, Suspension of speed monitoring - see error code.
Bit 21, Power up self test warning
•
Bit 21 = 0, No change in state.
•
Bit 21 = 1, A power-up self-test warning is issued.
Bit 22, Digital input 1 offline test warning
•
Bit 22 = 0, No change in state.
•
Bit 22 = 1, Digital input 1 offline test warning.
Bit 23, Digital input 2 offline test warning
•
Bit 23 = 0, No change in state.
•
Bit 23 = 1, Digital input 2 offline test warning.
Bits 24–31
These bits indicate a reason for internal or external errors. For more information, see the error codes.
Parameter 42-91 Safe Option Status 2
indicates which digital input of the safety option is activated, in pending state or in blank initial
state.
Configuring the Safety Option
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578
40 | Danfoss A/S © 2020.02