Procedure
1. In the
Siemens TIA Portal
, select
Open the project view
.
2. Double-click
Devices and Networks
.
The
Hardware Configuration
dialog box opens.
3. Select the Danfoss device in the network view and drag it into the workspace.
e3
0b
e0
85
.1
1
The project view shows the F-PLC and the Danfoss device.
e3
0b
e0
86
.1
1
4. In the
Password for Safety Program
dialog box, enter the appropriate password.
5. Assign the name to the Danfoss device. The name must be the same is shown in
parameter 12-08 Host Name
.
e3
0b
e0
87
.1
1
6. Select the following I/O protocol:
PROFIsafe 30 -6/6 Bytes, Standard Telegram 30
.
Configuring the Safety Option
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578
46 | Danfoss A/S © 2020.02