8.2.8 6-** Analog In/Out
Parameter group for configuration of the analog input and output.
6-00 Live Zero Timeout Time
Range:
Function:
10 s*
[1 - 99 s]
Enter the Live Zero Time-out time period. Live Zero Time-out Time is active for analog inputs, i.e.
terminal 53 or terminal 54, used as reference or feedback sources. If the reference signal value
associated with the selected current input falls below 50% of the value set in par. 6-10
, par. 6-12
Terminal 53 Low Current
par. 6-22
Terminal 54 Low Current
for a time period longer than the time set in par. 6-00
, the function selected in par. 6-01
6-01 Live Zero Timeout Function
Option:
Function:
Select the time-out function. The function set in par. 6-01
will be acti-
vated if the input signal on terminal 53 or 54 is below 50% of the value in par. 6-10
, par. 6-12
Terminal 53 Low Current
par. 6-22
Terminal 54 Low Current
for a time period defined in par. 6-00
If several time-outs occur simultaneously, the frequency converter prioritises the time-out functions
as follows:
1.
2.
par. 8-04
Control Timeout Function
The output frequency of the frequency converter can be:
•
[1] frozen at the present value
•
[2] overruled to stop
•
[3] overruled to jog speed
•
[4] overruled to max. speed
•
[5] overruled to stop with subsequent trip
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
Automation VT Drive FC322
Instruction Manual
8 How to Programme the Frequency Converter
MG.20.U1.22
99