EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0-100%
Output signal 0 or 4 mA is needed at 0% (50% of range) - set par. 6-51
to 50%
Output signal 20 mA is needed at 100% (75% of range) - set par. 6-52
EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0-10 mA
Output signal 0 or 4 mA is needed at Min ref - set par. 6-51
to 0%
Output signal 10 mA is needed at Max ref (100% of range) - set par. 6-52
to 200%
(20 mA / 10 mA x 100%=200%).
8.2.9 Drive Closed Loop, 20-**
This parameter group is used for configuring the closed loop PID Controller, that controls the output frequency of the frequency converter.