The GLCP can now be connected to another frequency converter and the parameter settings copied to this frequency converter.
Data transfer from to Frequency converter:
1.
Go to par. 0-50
LCP Copy
2.
Press the [OK] key
3.
Select “All from ”
4.
Press the [OK] key
The parameter settings stored in the GLCP are now transferred to the frequency converter indicated by the progress bar. When 100% is reached, press
[OK].
7.1.10 Initialisation to Default Settings
There are two ways to initialise the frequency converter to default: Recommended initialisation and manual initialisation.
Please be aware that they have different impact according to the below description.
Recommended initialisation (via par. 14-22
Operation Mode
)
1.
Select par. 14-22
Operation Mode
2.
Press [OK]
3.
Select “Initialisation” (for NLCP select “2”)
4.
Press [OK]
5.
Remove power to unit and wait for display to turn off.
6.
Reconnect power and the frequency converter is reset. Note
that first start-up takes a few more seconds
7.
Press [Reset]
par. 14-22
Operation Mode
initialises all except:
par. 14-50
RFI Filter
par. 8-30
Protocol
par. 8-31
Address
par. 8-32
Baud Rate
par. 8-35
Minimum Response Delay
par. 8-36
Max Response Delay
par. 8-37
Maximum Inter-Char Delay
par. 15-00
Operating Hours
to par. 15-05
Over Volt's
par. 15-20
Historic Log: Event
to par. 15-22
Historic Log: Time
par. 15-30
Alarm Log: Error Code
to par. 15-32
Alarm Log: Time
NB!
Parameters selected in par. 0-25
My Personal Menu
, will stay present, with default factory setting.
Manual initialisation
NB!
When carrying out manual initialisation, serial communication, RFI filter settings and fault log settings are reset.
Removes parameters selected in par. 0-25
My Personal Menu
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while
power up for Graphical LCP (GLCP)
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s
4. The frequency converter is now programmed according to
default settings
This parameter initialises all except:
par. 15-00
Operating Hours
par. 15-03
Power Up's
par. 15-04
Over Temp's
par. 15-05
Over Volt's
Automation VT Drive FC322
Instruction Manual