1-24 Motor Current
Range:
Function:
Application
dependent*
[Application dependant]
Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection etc.
NB!
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range:
Function:
Application
dependent*
[100 - 60000 RPM]
Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu-
lating automatic motor compensations.
NB!
This parameter cannot be changed while the motor is running.
1-29 Automatic Motor Adaptation (AMA)
Option:
Function:
The AMA function optimizes dynamic motor performance by automatically optimizing the advanced
motor parameters par. 1-30
Stator Resistance (Rs)
to par. 1-35
Main Reactance (Xh)
) while the
motor is stationary.
[0] *
Off
No function
[1]
Enable complete AMA
performs AMA of the stator resistance R
S
, the rotor resistance R
r
, the stator leakage reactance X
1
,
the rotor leakage reactance X
2
and the main reactance X
h
.
[2]
Enable reduced AMA
performs a reduced AMA of the stator resistance R
s
in the system only. Select this option if an LC
filter is used between the frequency converter and the motor.
Activate the AMA function by pressing [Hand on] after selecting [1] or [2]. See also the section
Automatic Motor Adaptation
. After a normal sequence,
the display will read: “Press [OK] to finish AMA”. After pressing the [OK] key the frequency converter is ready for operation.
Note:
•
For the best adaptation of the frequency converter, run AMA on a cold motor
•
AMA cannot be performed while the motor is running
NB!
It is important to set motor par. 1-2* Motor Data correctly, since these form part of the AMA algorithm. An AMA must be performed
to achieve optimum dynamic motor performance. It may take up to 10 min., depending on motor power rating.
NB!
Avoid generating external torque during AMA
8 How to Programme the Frequency Converter
Automation VT Drive FC322
Instruction Manual
86
MG.20.U1.22
8