
22-50 End of Curve Function
Option:
Function:
[0] *
Off
End of Curve monitoring not active.
[1]
Warning
A warning is issued in the display [W94].
[2]
Alarm
An alarm is issued and the frequency converter trips. A message [A94] appears in the display.
[3]
Manual Reset Alarm
NB!
Automatic restart will reset the alarm and start the system again.
22-51 End of Curve Delay
Range:
Function:
10 s*
[0 - 600 s]
When an End of Curve condition is detected, a timer is activated. When the time set in this parameter
expires, and the End of Curve condition has been steady in the entire period, the function set in
par. 22-50
will be activated. If the condition disappears before the timer
expires, the timer will be reset.
22-80 Flow Compensation
Option:
Function:
[0] *
Disabled
[0]
Disabled
: Set-Point compensation not active.
[1]
Enabled
[1]
Enabled
:Set-Point compensation is active. Enabling this parameter allows the Flow Compensated
Setpoint operation.
22-81 Square-linear Curve Approximation
Range:
Function:
100 %*
[0 - 100 %]
Example 1:
Adjustment of this parameter allows the shape of the control curve to be adjusted.
0 = Linear
100% = Ideal shape (theoretical).
NB!
Please note: Not visible when running in cascade.
8 How to Programme the Frequency Converter
Automation VT Drive FC322
Instruction Manual
112
MG.20.U1.22
8