DC Link Voltage [V]
Variable
name:
SNVT
type:
Value:
nvoDCVoltage
SNVT_volt
Min.
Max.
Resolution:
0 V
10,000 V
0.1 V
This variable contains the measured Dc-link voltage. The value is filtered and therefore may be delayed with up to 1.3 seconds before a voltage change
is reflected in the output variable.
Motor Thermal [%]
Variable
name:
SNVT
type:
Value:
nvoTempMrt
SNVT_lev_cont
Min.
Max.
Resolution:
0 %
100 %
0.5 %
This variable contains the calculated / estimated thermal load on the motor.
The cut-out limit is at 100%.
Inverter Thermal [%]
Variable
name:
SNVT
type:
Value:
nvoTempInvrtr
SNVT_lev_cont
Min.
Max.
Resolution:
0 %
100 %
0.5 %
This variable contains the percentage thermal load of the inverters.
The cut-out limit is at 100%.
Closed Loop Feedback
Variable
name:
SNVT
type:
Value:
nvoFeedback
SNVT_count_inc_f
Min.
Max.
Resolution:
0 %
100 %
0.5 %
This variable contains the summerized amount of network feedback in closed loop mode.
Fanbelt broken
Variable
name:
SNVT
type:
State:
Value:
Command:
nvoBrokenbelt
SNVT_switch
0 (False)
Any
Fanbelt not broken
1 (True)
Any
Fanbelt broken
This variable indicates whether the fanbelt is intact or broken (indicated by bit 8 in Warning Word 2).
5 Configuration of the system
VLT® FC 100 LonWorks
28
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
5