6.2 Danfoss FC Control Profile
6.2.1 FC Control Profile
Control Word According to FC Profile
(Par. 8-10 set to
FC Profile
)
Bit
Bit value=0
Bit value=1
00
Reference value
External selection lsb
01
Reference value
External selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output freq.
Use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 04 active
13
Parameter set-up
Selection lsb
14
Parameter set-up
Selection msb
15
No function
Reverse
6.2.2 Explanation of the Control Bits
Bits 00 and 01:
Bits 00 and 01 are used to choose between the four reference values,
which are pre-programmed in par. 3-10
Preset Reference
in accordance
with the following table:
Programmed ref. value
Parameter
Bit 01
Bit
00
1
3-10 [0]
0
0
2
3-10 [1]
0
1
3
3-10 [2]
1
0
4
3-10 [3]
1
1
NB!
, a selection is
made to define how Bit 00/01 gates with the corre-
sponding function on the digital inputs.
Bit 02, DC brake:
Bit 02 set to [0] leads to DC braking and stop of the motor. Braking cur-
rent and duration are set in par. 2-01
DC Brake Current
and par. 2-02
DC
Braking Time
.
Bit 02 set to [1] leads to ramping.
Bit 03, Coasting:
Bit 03 set to [0] causes the frequency converter to immediately release
of the motor (the output transistors are "shut off"), so that it coasts to a
standstill.
Bit 03 set to [1] enables the frequency converter to start the motor if
other starting conditions have been fulfilled.
NB!
, a selection is made to de-
fine how Bit 03 gates with the corresponding function
on a digital input.
Bit 04, Quick Stop:
Bit 04 set to [0] causes a stop in which the motor speed is ramped down
to stop via par. 3-81
Quick Stop Ramp Time
.
Bit 05, Hold output frequency:
Bit 05 set to [0] causes the present output frequency (Hz) to freeze. The
frozen output frequency can then be changed only by means of the digital
inputs set by par. 5-10 to 5-15, programmed to [Speed up] or [Speed
down].
NB!
If [Freeze output] is active, the frequency converter
can only be stopped by the following:
•
Bit 03 Coasting stop
•
Bit 02 DC braking
•
Digital input (par. 5-10 to 5-15) programmed
to DC braking, Coasting stop or Reset and
coasting stop.
6 How to control the Frequency Converter
VLT® FC 100 LonWorks
42
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark