20-07 Feedback 3 Conversion
Option:
Function:
See par. 20-01
Feedback 1 Conver-
sion
for details.
[0]
*
Linear
[1]
Square root
[2]
Pressure to temperature
[3]
Pressure to flow
[4]
Velocity to flow
20-08 Feedback 3 Source Unit
Option:
Function:
See par. 20-02
Feedback 1 Source Unit
for details.
20-12 Reference/Feedback Unit
Option:
Function:
See par. 20-02
Feedback 1 Source Unit
for details.
20-13 Minimum Reference/Feedb.
Range:
Function:
0.000
ProcessCtr-
lUnit
*
[Applica-
tion
depend-
ant]
Enter the desired minimum value for
the remote reference when operating
with par. 1-00
Configuration Mode
set
for Closed Loop [3] operation. Units are
set in par. 20-12
Reference/Feedback
Unit
.
Minimum feedback will be -200% of
either the value set in
par. 20-13
Minimum Reference/Feedb.
or
in par. 20-14
Maximum Reference/
Feedb.
, which ever numeric value is the
highest.
NOTE
If operating with par. 1-00
Configuration Mode
set for
Open Loop [0], par. 3-02
Minimum Reference
must be
used.
20-14 Maximum Reference/Feedb.
Range:
Function:
100.000
ProcessCtrlU-
nit
*
[Applica-
tion
dependant]
Enter the maximum reference/
feedback for closed loop operation.
The setting determines the highest
value obtainable by summing all
reference sources for closed loop
operation. The setting determines
100% feedback in open and closed
loop (total feedback range: -200% to
+200%).
NOTE
If operating with par. 1-00
Configuration Mode
set for
Open Loop [0], par. 3-03
Maximum Reference
must be
used.
NOTE
The dynamics of the PID controller will depend on the
value set in this parameter. Please see also par. 20-93
PID
Proportional Gain
.
Par. 20-13 and par. 20-14 also determine the feedback
range when using feedback for display readout with
par. 1-00
Configuration Mode
set for Open Loop [0].
Same condition as above.
20-20 Feedback Function
Option:
Function:
This parameter determines how the three possible
feedbacks will be used to control the output
frequency of the frequency converter.
[0]
Sum
Sum
[0] sets up the PID Controller to use the sum
of Feedback 1, Feedback 2 and Feedback 3 as the
feedback.
NOTE
Any unused feedbacks must be set to
No
Function
in par. 20-00
Feedback 1 Source
,
par. 20-03
Feedback 2 Source
, or
par. 20-06
Feedback 3 Source
.
The sum of Setpoint 1 and any other references
that are enabled (see par. group 3-1*) will be used
as the PID Controller’s set-point reference.
[1]
Difference
Difference
[1] sets up the PID controller to use the
difference between Feedback 1 and Feedback 2 as
the feedback. Feedback 3 will not be used with
this selection. Only Setpoint 1 will be used. The
sum of Setpoint 1 and any other references that
are enabled (see par. group 3-1*) will be used as
the PID controller’s set-point reference.
[2]
Average
Average
[2] sets up the PID Controller to use the
average of Feedback 1, Feedback 2 and Feedback
3 as the feedback.
NOTE
Any unused feedbacks must be set to
No
Function
in par. 20-00
Feedback 1 Source
,
par. 20-03
Feedback 2 Source
, or
par. 20-06
Feedback 3 Source
. The sum of
Setpoint 1 and any other references that
are enabled (see par. group 3-1*) will be
used as the PID Controller’s set-point
reference.