Unsuccessful AMA
1.
The frequency converter enters into alarm mode. A
description of the alarm can be found in the
Trouble-
shooting
section.
2.
"Report Value” in the [Alarm Log] shows the last
measuring sequence carried out by the AMA, before
the frequency converter entered alarm mode. This
number along with the description of the alarm will
assist troubleshooting. If contacting Danfoss Service,
make sure to mention number and alarm descrip-
tion.
NOTE
Unsuccessful AMA is often caused by incorrectly entered
motor name plate data or too big difference between
the motor power size and the frequency converter
power size.
Step 4: Set speed limit and ramp time
Set up the desired limits for speed and ramp time.
Par. 3-02
Minimum Reference
Par. 3-03
Maximum Reference
Par. 4-11
Motor Speed Low Limit [RPM]
or par. 4-12
Motor Speed Low Limit [Hz]
Par. 4-13
Motor Speed High Limit [RPM]
or par. 4-14
Motor Speed High Limit [Hz]
Par. 3-41
Ramp 1 Ramp Up Time
Ramp-up Time 1 [s]
Par. 3-42
Ramp 1 Ramp Down Time
Ramp-down Time 1 [s]
See the section
How to programme the frequency converter,
Quick Menu Mode
for an easy set-up of these parameters.
Electrical Installation
VLT
®
HVAC Drive Operating Instructions
46
MG.11.AD.02 - VLT
®
is a registered Danfoss trademark
4
4