7.3.23 25-** Cascade Pack Controller
Par. No. # Parameter description
Default value
4-set-up
Change during
operation
Conver-
sion index
Type
25-0* System Settings
25-00
Cascade Controller
[0] Disabled
2 set-ups
FALSE
-
Uint8
25-02
Motor Start
[0] Direct on Line
2 set-ups
FALSE
-
Uint8
25-04
Pump Cycling
[0] Disabled
All set-ups
TRUE
-
Uint8
25-05
Fixed Lead Pump
[1] Yes
2 set-ups
FALSE
-
Uint8
25-06
Number of Pumps
2 N/A
2 set-ups
FALSE
0
Uint8
25-2* Bandwidth Settings
25-20
Staging Bandwidth
10 %
All set-ups
TRUE
0
Uint8
25-21
Override Bandwidth
100 %
All set-ups
TRUE
0
Uint8
25-22
Fixed Speed Bandwidth
casco_staging_bandwidt
h (P2520)
All set-ups
TRUE
0
Uint8
25-23
SBW Staging Delay
15 s
All set-ups
TRUE
0
Uint16
25-24
SBW Destaging Delay
15 s
All set-ups
TRUE
0
Uint16
25-25
OBW Time
10 s
All set-ups
TRUE
0
Uint16
25-26
Destage At No-Flow
[0] Disabled
All set-ups
TRUE
-
Uint8
25-27
Stage Function
[1] Enabled
All set-ups
TRUE
-
Uint8
25-28
Stage Function Time
15 s
All set-ups
TRUE
0
Uint16
25-29
Destage Function
[1] Enabled
All set-ups
TRUE
-
Uint8
25-30
Destage Function Time
15 s
All set-ups
TRUE
0
Uint16
25-4* Staging Settings
25-40
Ramp Down Delay
10.0 s
All set-ups
TRUE
-1
Uint16
25-41
Ramp Up Delay
2.0 s
All set-ups
TRUE
-1
Uint16
25-42
Staging Threshold
SR
All set-ups
TRUE
0
Uint8
25-43
Destaging Threshold
SR
All set-ups
TRUE
0
Uint8
25-44
Staging Speed [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
25-45
Staging Speed [Hz]
0.0 Hz
All set-ups
TRUE
-1
Uint16
25-46
Destaging Speed [RPM]
0 RPM
All set-ups
TRUE
67
Uint16
25-47
Destaging Speed [Hz]
0.0 Hz
All set-ups
TRUE
-1
Uint16
25-5* Alternation Settings
25-50
Lead Pump Alternation
[0] Off
All set-ups
TRUE
-
Uint8
25-51
Alternation Event
[0] External
All set-ups
TRUE
-
Uint8
25-52
Alternation Time Interval
24 h
All set-ups
TRUE
74
Uint16
25-53
Alternation Timer Value
0 N/A
All set-ups
TRUE
0
VisStr[7]
25-54
Alternation Predefined Time
SR
All set-ups
TRUE
0
TimeOfDayWo-
Date
25-55
Alternate if Load < 50%
[1] Enabled
All set-ups
TRUE
-
Uint8
25-56
Staging Mode at Alternation
[0] Slow
All set-ups
TRUE
-
Uint8
25-58
Run Next Pump Delay
0.1 s
All set-ups
TRUE
-1
Uint16
25-59
Run on Mains Delay
0.5 s
All set-ups
TRUE
-1
Uint16
25-8* Status
25-80
Cascade Status
0 N/A
All set-ups
TRUE
0
VisStr[25]
25-81
Pump Status
0 N/A
All set-ups
TRUE
0
VisStr[25]
25-82
Lead Pump
0 N/A
All set-ups
TRUE
0
Uint8
25-83
Relay Status
0 N/A
All set-ups
TRUE
0
VisStr[4]
25-84
Pump ON Time
0 h
All set-ups
TRUE
74
Uint32
25-85
Relay ON Time
0 h
All set-ups
TRUE
74
Uint32
25-86
Reset Relay Counters
[0] Do not reset
All set-ups
TRUE
-
Uint8
25-9* Service
25-90
Pump Interlock
[0] Off
All set-ups
TRUE
-
Uint8
25-91
Manual Alternation
0 N/A
All set-ups
TRUE
0
Uint8
How to Programme the Frequ...
VLT
®
HVAC Drive Operating Instructions
MG.11.AD.02 - VLT
®
is a registered Danfoss trademark
121