Non-UL compliance fuses
Frequency
converter
Max. fuse size
Voltage
Type
200-240 V - T2
1K1-1K5
16A
1
200-240 V
type gG
2K2
25A
1
200-240 V
type gG
3K0
25A
1
200-240 V
type gG
3K7
35A
1
200-240 V
type gG
5K5
50A
1
200-240 V
type gG
7K5
63A
1
200-240 V
type gG
11K
63A
1
200-240 V
type gG
15K
80A
1
200-240 V
type gG
18K5
125A
1
200-240 V
type gG
22K
125A
1
200-240 V
type gG
30K
160A
1
200-240 V
type gG
37K
200A
1
200-240 V
type aR
45K
250A
1
200-240 V
type aR
380-480 V - T4
1K1-1K5
10A
1
380-500 V
type gG
2K2-3K0
16A
1
380-500 V
type gG
4K0-5K5
25A
1
380-500 V
type gG
7K5
35A
1
380-500 V
type gG
11K-15K
63A
1
380-500 V
type gG
18K
63A
1
380-500 V
type gG
22K
63A
1
380-500 V
type gG
30K
80A
1
380-500 V
type gG
37K
100A
1
380-500 V
type gG
45K
125A
1
380-500 V
type gG
55K
160A
1
380-500 V
type gG
75K
250A
1
380-500 V
type aR
90K
250A
1
380-500 V
type aR
1) Max. fuses - see national/international regulations for selecting an applicable fuse size.
Table 4.3: Non-UL fuses 200 V to 480 V
If UL/cUL is not to be complied with, we recommend using the
following fuses, which will ensure compliance with EN50178:
Frequency Converter
Voltage
Type
P110 - P250
380 - 480 V
type gG
P315 - P450
380 - 480 V
type gR
Table 4.4: Compliance with EN50178
Electrical Installation
VLT
®
HVAC Drive Operating Instructions
MG.11.AD.02 - VLT
®
is a registered Danfoss trademark
23
4
4