4-13 Motor Speed High Limit [RPM]
Range:
Function:
Application
depend-
ent
*
[Applica-
tion
dependant]
Enter the maximum limit for motor
speed. The Motor Speed High Limit can
be set to correspond to the manufactur-
er’s maximum rated motor. The Motor
Speed High Limit must exceed the
setting in par. 4-11
Motor Speed Low
Limit [RPM]
. Only par. 4-11
Motor Speed
Low Limit [RPM]
or par. 4-12
Motor Speed
Low Limit [Hz]
will be displayed depend-
ing on other parameters in the Main
Menu and depending on default
settings dependant on global location.
NOTE
Max. output frequency cannot exceed 10% of the
inverter switching frequency (par. 14-01
Switching
Frequency
).
NOTE
Any changes in par. 4-13
Motor Speed High Limit [RPM]
will reset the value in par. 4-53
Warning Speed High
to
the same value as set in par. 4-13
Motor Speed High Limit
[RPM]
.
4-14 Motor Speed High Limit [Hz]
Range:
Function:
Application
depend-
ent
*
[Applica-
tion
dependant]
Enter the maximum limit for motor
speed. The Motor Speed High Limit can
be set to correspond to the manufactur-
er’s recommended maximum of the
motor shaft. The Motor Speed High Limit
must exceed the in par. 4-12
Motor
Speed Low Limit [Hz]
. Only
par. 4-11
Motor Speed Low Limit [RPM]
or
par. 4-12
Motor Speed Low Limit [Hz]
will
be displayed depending on other
parameters in the Main Menu and
depending on default settings depend-
ant on global location.
NOTE
Max. output frequency cannot exceed 10% of the
inverter switching frequency (par. 14-01
Switching
Frequency
).
4-53 Warning Speed High
Range:
Function:
Application
depend-
ent
*
[Applica-
tion
dependant]
Enter the n
HIGH
value. When the motor
speed exceeds this limit (n
HIGH
), the
display reads SPEED HIGH. The signal
outputs can be programmed to produce
a status signal on terminal 27 or 29 and
on relay output 01 or 02. Programme
4-53 Warning Speed High
Range:
Function:
the upper signal limit of the motor
speed, n
HIGH
, within the normal working
range of the frequency converter. Refer
to the drawing in this section.
NOTE
Any changes in par. 4-13
Motor Speed High Limit [RPM]
will reset the value in par. 4-53
Warning Speed High
to
the same value as set in par. 4-13
Motor Speed High Limit
[RPM]
.
If a different value is needed in par. 4-53
Warning Speed
High
, it must be set after programming of
par. 4-13
Motor Speed High Limit [RPM]
4-56 Warning Feedback Low
Range:
Function:
-999999.999
ProcessCtrlU-
nit
*
[Application
dependant]
Enter the lower feedback limit.
When the feedback falls below this
limit, the display reads Feedb Low.
The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 and on
relay output 01 or 02.
4-57 Warning Feedback High
Range:
Function:
999999.999
ProcessCtrlU-
nit
*
[Application
dependant]
Enter the upper feedback limit.
When the feedback exceeds this
limit, the display reads Feedb High.
The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 and on
relay output 01 or 02.
4-64 Semi-Auto Bypass Set-up
Option:
Function:
[0]
*
Off
No function
[1]
Enabled Starts the Semi-Automatic Bypass set-up and
continue with the procedure described above.
How to Programme the Frequ...
VLT
®
HVAC Drive Operating Instructions
76
MG.11.AD.02 - VLT
®
is a registered Danfoss trademark
7
7