MENU > Settings > Control parameters 1
Position (A333.2 / A333.3)
Read-out
Circuit
Setting range
Factory setting
1
-
*)
Position of the motorized control valve M1 is indicated as a % value.
A 0 - 10 volt signal comes from a position measuring in M1 and is applied to
input S11 (ECA 32). This input voltage is converted to the displayed % value.
Access to conversion (scale) settings.
*)
2.0 volt = 0 %, 10.0 volt = 100 %
The position is measured by means of a 0 - 10 volt signal.
The measured voltage must be converted to a position value by
the controller.
The following procedure sets up the conversion:
Push the dial to see the graph and enter the value sets for the 2
input voltages and related position values.
Position value range: 0 … 100 %
The factory set voltage values (2.0 volt and 10.0 volt) can be
changed in the following two separate menus "Low X" and "High X".
Factory settings: 2.0 , 0 (= 2.0 V / 0 %) and 10.0,100 (= 10.0 V / 100 %)
This means that the "Position" is 0 % at 2.0 V and 100 % at 10.0 V.
Typically, the higher the voltage, the higher the displayed position.
X = Volt
Y = Position
This scaling menu is always displayed, regardless a position signal
is applied.
The position is indicated as 0 when the position signal is not applied.
MENU > Settings > Control parameters 1
Filter constant
1x113
The value of the filter constant determines the dampening of the measured
value.
The higher the value, the more dampening.
By this, a too quick change of the measured value can be avoided.
See Appendix “Parameter ID overview”
Minor
value:
Lower dampening
Major
value:
Higher dampening
88 | © Danfoss | 2017.09
VI.GU.T2.02
Operating Guide ECL Comfort 310, application A333