![Danfoss ECL Comfort 310 Operating Manual Download Page 167](http://html1.mh-extra.com/html/danfoss/ecl-comfort-310/ecl-comfort-310_operating-manual_506775167.webp)
ID
Parameter Name
A333.x
Setting range
Factory
Unit
Own settings
11148
Lower difference
1, 2, 3
OFF, 1 ... 30
OFF
K
11149
Delay
1, 2, 3
0 ... 250
180
Sec
11150
Lowest temp.
1, 2, 3
10 ... 50
30
°C
11174
Motor pr.
1, 2, 3
OFF, 10 ... 59
OFF
Min
11177
Temp. min.
1, 2, 3
10 ... 150
10
°C
11178
Temp. max.
1, 2, 3
10 ... 150
90
°C
11179
Summer, cut-out
1, 2, 3
OFF, 1 ... 50
20
°C
11184
Xp
1, 2, 3
5 ... 250
80
K
11185
Tn
1, 2, 3
1 ... 999
30
Sec
11186
M run
1, 2
5 ... 250
60
Sec
11187
Nz
1, 2, 3
1 ... 9
3
K
11189
Min. act. time
1, 2
2 ... 50
10
11310
Retry time
1, 2, 3
OFF, 1 ... 99
OFF
Min
11311
Change, duration
1, 2, 3
1 ... 60
7
11312
Change time
1, 2, 3
0 ... 23
12
11313
Stab. time
1, 2, 3
1 ... 99
50
Sec
11314
Chan.-over time
1, 2, 3
OFF, 1 ... 99
15
Sec
11316
Alarm handling
1, 2, 3
OFF ; ON
OFF
11318
Max. pressure
1, 2, 3
0.0 ... 40.0
40.0
Bar
11319
Max. press. diff.
1, 2, 3
-5.0 ... -0.1
-0.5
Bar
11320
P exercise
1, 2, 3
OFF, 1 ... 200
OFF
Sec
11321
Pressure, des.
1, 2, 3
0.2 ... 25.0
3.0
Bar
11322
Pressure, diff.
1, 2, 3
0.1 ... 5.0
1.5
Bar
11323
Time-out
1, 2, 3
1 ... 1000
10
Min
11325
Valve delay
1, 2, 3
0 ... 30
1
Sec
11326
No. of pumps
1, 2, 3
1 ... 2
1
11330
Wake up level
2, 3
0 ... 100
40
%
11331
Sleep level
2, 3
OFF, 1 ... 100
20
%
11332
Sleep mode time
2, 3
0 ... 300
10
Sec
11333
Boost
2, 3
0 ... 100
5
%
11500
Send desired T
1, 2, 3
OFF ; ON
ON
11607
Low X
1, 2, 3
0.0 ... 10.0
2.0
V
11608
High X
1, 2, 3
0.0 ... 10.0
10.0
V
11609
Low Y
1, 2, 3
0.0 ... 25.0
0.0
Bar
11610
High Y
1, 2, 3
0.0 ... 25.0
25.0
Bar
11614
Alarm high
1, 2, 3
0.0 ... 25.0
25.0
Bar
11615
Alarm low
1, 2, 3
0.0 ... 25.0
0.0
Bar
11617
Alarm time-out
1, 2, 3
0 ... 100
10
Min
12113
Filter constant
1, 2, 3
1 ... 250
2
12165
V out max.
2, 3
0 ... 100
100
%
12167
V out min.
2, 3
0 ... 100
0
%
VI.GU.T2.02
© Danfoss | 2017.09 | 167
Operating Guide ECL Comfort 310, application A333