MENU > Settings > Control parameters 1
Low X
1x607
Definition of which voltage value corresponds to which position value.
The voltage (as a 0 - 10 volt signal) comes from a position measuring in
M1 and is applied to input S11 (ECA 32). This input voltage is converted to
display a % value for the position of M1.
See also "Position" and "High X".
See Appendix “Parameter ID overview”
X
= Volt
Y
= Position
# 1 # = Low X
MENU > Settings > Control parameters 1
High X
1x608
Definition of which voltage value corresponds to which position value.
The voltage (as a 0 - 10 volt signal) comes from a position measuring in
M1 and is applied to input S11 (ECA 32). This input voltage is converted to
display a % value for the position of M1.
See also "Position" and "Low X".
See Appendix “Parameter ID overview”
X
= Volt
Y
= Position
# 1 # = High X
MENU > Settings > Control parameters 1
Motor pr. (motor protection)
1x174
Prevents the controller from unstable temperature control (and resulting
actuator oscillations). This can occur at very low load. The motor protection
increases the lifetime of all involved components.
See Appendix “Parameter ID overview”
OFF:
Motor protection is not activated.
Value:
Motor protection is activated after the set activation
delay in minutes.
VI.GU.T2.02
© Danfoss | 2017.09 | 89
Operating Guide ECL Comfort 310, application A333