MENU > Settings > Refill water
Time-out
11323
Circuit
Setting range
Factory setting
1
1 . . . 1000 sec
100 sec
Setting of the max. time for refill. The pressure, measured by S10, must be
OK within the set time.
If not, the refill water function stops and an alarm is activated.
X
= Time
# 1 # = Pressure OK / not OK
# 2 # = Refill pump 3 or 4
# 3 # = Time-out
X
= Time
# 1 # = Pressure OK / not OK
# 2 # = Refill pump 3 or 4
# 3 # = Time-out
# 4 # = Alarm
The "Time-out" function is disabled when "Alarm handling" (ID no.
12316) is set to OFF.
VI.GU.T2.02
© Danfoss | 2017.09 | 107
Operating Guide ECL Comfort 310, application A333