MENU > Settings > Refill water
P exercise (pump exercise)
11022
Circuit
Setting range
Factory setting
1
OFF / 1 ... 200 s
OFF
The time the pump is activated during exercise. Exercise takes place every
day (at 12:00).
OFF:
No pump exercise.
1 ... 200:
Activation time during exercise.
The feedback from the pressure at S10 is active and will activate the
alarm in case that the pump does not start.
MENU > Settings > Refill water
Valve delay
11325
Circuit
Setting range
Factory setting
1
0 ... 30 s
1 sec
Setting of the time for activation of the ON/OFF valve after start of the refill
water pump.
X
= Time
Y
= Pressure
# 1 # = Max. pressure
# 2 # = Actual pressure
# 3 # = Max. pressure difference
# 4 # = Valve delay
MENU > Settings > Refill water
No. of pumps
11326
Circuit
Setting range
Factory setting
1
1 / 2
1
Choose the number of refill water pumps in the system.
108 | © Danfoss | 2017.09
VI.GU.T2.02
Operating Guide ECL Comfort 310, application A333