MENU > Settings > Flow meter
Low X (A333.2 / A333.3)
17607
Circuit
Setting range
Factory setting
1
0.0 . . . 10.0 V
2.0 V
Definition of which voltage value corresponds to which water flow value.
The voltage (as a 0 - 10 volt signal) comes from a flow meter and is applied
to input S13 (ECA 32).
This input voltage is converted to display a water flow value (in m
3
/ h).
See also "Actual" and "High X".
X
= Volt
Y
= Flow (m
3
/ h)
# 1 # = Low X
MENU > Settings > Flow meter
High X (A333.2 / A333.3)
17608
Circuit
Setting range
Factory setting
1
0.0 . . . 10.0 V
10.0 V
Definition of which voltage value corresponds to which water level value.
The voltage (as a 0 - 10 volt signal) comes from a flow meter and is applied
to input S13 (ECA 32).
This input voltage is converted to display a water flow value (in m
3
/ h).
See also "Actual" and "Low X".
X
= Volt
Y
= Flow (m
3
/ h)
# 1 # = High X
MENU > Settings > Flow meter
Input type (A333.2 / A333.3)
17109
Circuit
Setting range
Factory setting
1
AM1 / IM1 / EM1 . . . EM5 / OFF
OFF
Setting of the signal type from the flow meter F2.
AM1:
F2 sends analogue signal (0 - 10 volt), applied to S13 on
ECA 32.
IM1:
F2 sends pulse signal, applied to "Pulse 2" on ECA 32.
EM1 - EM5:
F2 sends signal via M-Bus.
OFF:
No F2 signal.
VI.GU.T2.02
© Danfoss | 2017.09 | 119
Operating Guide ECL Comfort 310, application A333