10 | © Danfoss | 2019.02

VI.IR.V1.

9Z

 

AMEi 6

ENGLISH

Safety Notes

To avoid personal injury and damage 

to devices, it is absolutely essential for 

these instructions and safety notes to 

be read carefully and reviewed prior to 

assembly and use.
Do not dismantle actuator with the safety spring 

function! There is risk of injury and death in the 

event of improper handling!
The actuator is heavy. Handle with care to avoid 

injury or product damage.

Disposal

This product should be dismantled 

and its components sorted, if possible, 

in various groups before recycling or 

disposal.

Always follow the local disposal regulations.

Wiring

Do not touch anything on the PCB!  

Do not remove the service cover 

before the power supply is fully 

switched off.

Wiring length

Recommended cross-sectional 

area of the wiring

0-50 m

0,75 mm

2

> 50 m

1,5 mm

2

Electrical connection 

iNET actuator mounting to pressure 

actuator 

Stand-By mode for manual operation 

and differential pressure setting 

Set-point range see rating plate on the pressure 

actuator*

1.  Start-up of system *

2. Set flow rate on a motorized valve over 

which the differential pressure is controlled, 

to about 50 % *

3. Adjustment

• Observe pressure indica tors *

Enter the Stand-By mode for manual 

operation

•  Pushing the button 

 on the actuator 

increases the set-point (squeezing the 

spring)

•  Pushing the button 

 redu ces the  

set-point (stretching the spring)

End switch setting for  MIN/MAX set Δp 

Slider 

 can be set to limit min. ∆p 

Slider 

 can be set to limit max. ∆p;

Fix the sliders 

 with 2 srews 

Slider 

 may be sealed 

see instruction for relevant combination

pressure actuator/ valve

DIP switch setting 

S1

S1/DIP 1

Input signal type selector: 

OFF: Input signal Y is set to voltage (V) 

ON:  Input signal Y is set to current (mA) 

S1/DIP 2

Output signal type selector:

 

OFF: Output signal X is set to voltage (V) 

ON:  Output signal X is set to current (mA)

S1/DIP 3

Direct or inverse acting selector 

(Fig. 2)

:

 

OFF: Actuator is direct acting to input 

signal 

ON:  Actuator is inverse (reverse) acting 

to control signal (only for AMEI 6 iNET in 

combination with AFA 2) 

S1/DIP 4

 

Normal or sequential mode selector:

OFF: Actuator is working in range 0(2)-10 V 

or 0(4)-20 mA. 

ON:  Actuator is working in sequential 

range; 0-5 V or (0-10 mA) or (5-10 V) or (10-

20 mA). 

Signal range selector S1/DIP 6 sets the 

sequential range

S1/DIP 5

 

0-10 V/2-10 V – Input/output

OFF: 0-10 V; input signal is in the range 

from 0-10 V (voltage input) or from 0-20 

mA (current input) 

ON:  2 –10 V; input signal is in the range 

from 2-10 V (voltage input) or from 4-20 mA 

(current input) 

Signal range selector S1/DIP 1 & DIP 2 sets 

Y and X signal. 

S1/DIP 6

 

Sequential range selector:

OFF:  0-5 V or (0-10 mA) 

ON:   5-10 V or (10-20 mA). 

[S1/DIP 4 = ON!] 

S1/DIP 7

 

Not used

S1/DIP 8

 

Not used

S2

S2/DIP 1 

Not used 

S2/DIP 2

 

Not used 

S2/DIP 3

 

Not used 

S2/DIP 4*

 

OFF: Analog signal (V/mA)

Actuator operates in 

analog mode

ON: MOD BUS 

Actuator operates in 

digital mode

*In 

analog mode S2/DIP 4 = OFF

,  DIP 

switches S1/DIP 1-7 work as active 

functions.

In 

digital mode S2/DIP 4 = ON

 , DIP 

switches S1/DIP 1-7 work as a digital 

addresses.

In digital mode Modbus RS485 could be 

used either for the monitoring  purposes or 

for the AMEi 6 actuator positioning..

3

Fig. 2

Calibration 

Calibration to the desired pressure actuator 

stroke (min-max spring setting). 

Before calibration drive the actuator out of end 

positions (minimal gap between sliders 

,

 

and pin on the end switch 

 has to be ensured).

To start calibration procedure, press and hold 

RESET button for 5 seconds until the green light 

starts flashing. End positions of the actuator are 

automatically adopted based on pre-set end 

switch positions sliders 

,

. Actuator goes 

to the stationary mode and starts responding 

to the control signal. Depends on min-max Δp 

setting (position of sliders 

 and 

), calibration 

may take up to ~1 h (in case of max available  Δp 

range-stroke is set).

Calibration procedure need to be repeated every 

time when min/max spring setting is changed 

(position of sliders 

 and 

 is changed).

LED signalisation 

Dimensions 

Summary of Contents for AMEi 6 iNET

Page 1: ...uatore elettrico intelligente AMEi 6 iNET www heating danfoss it Pagina 13 AMEi 6 iNET www heating danfoss cn 14 POLSKI Inteligentny si ownik elektryczny AMEi 6 iNET www heating danfoss pl Strona 15 A...

Page 2: ...ma di controll SCADA o altra HMI remota SCADA HMI System sterowania SCADA lub inny zdalny interfejs HMI SCADA AMEi 6 iNET Human machine interface Mensch Maschine Schnittstelle Interface homme machine...

Page 3: ...se Masse Terra Masa 4 1 only analog signal nur analoges Signal signal analogique uniquement solo segnale analogico tylko sygna analogowy 2 only Modbus signal nur Modbus Signal signal Modbus uniquement...

Page 4: ...4 Danfoss 2019 02 VI IR V1 9Z AMEi 6 min 65 1 36 mm 1 6 mm Click 150 mm 3x...

Page 5: ...nden lang gedruckt Deplacement AUTO pression maintenue pendant 10 s movimento AUTOMATICO premuto per 10s 10 AUTO ruch przyciskaj 10s 10 pressed for 1s 1 s lang gedruckt pression maintenue pendant 1 s...

Page 6: ...6 Danfoss 2019 02 VI IR V1 9Z AMEi 6 GREEN LED GREEN LED 5s RESET RESET S1 S2...

Page 7: ...s at the upper end position Normalbetrieb Stellantrieb stoppt in oberer Endlage Mode normal L actionneur s arr te en position de fin de course superieure Modalita normale L attuatore si ferma nella po...

Page 8: ...sk CI NI CIE SPR YNY 10 s Si ownik ciska spr yn SQUEEZE SPRING 10 Actuator is stretching the spring Stellantrieb fahrt die Feder auseinander L actionneur allonge le ressort L attuatore sta allungando...

Page 9: ...cazione Typ wskazania Modbus communication status Modbus Kommunikationsstatus Statut de la communication Modbus Stato della comunicazione Modbus Modbus Stan komunikacji Modbus No power supply Keine Sp...

Page 10: ...FF Actuator is direct acting to input signal ON Actuator is inverse reverse acting to control signal only for AMEI 6 iNET in combination with AFA 2 S1 DIP 4 Normal or sequential mode selector OFF Actu...

Page 11: ...t auf das Eingangssignal EIN Stellantrieb reagiert invers entgegengesetzt auf das Eingangssignal nur f r AMEI 6 iNET in Kombination mit AFA 2 S1 DIP 4 Normale oder sequentielle Einstellung AUS Stellan...

Page 12: ...actionneur agit directement sur le signal d entr e MARCHE L actionneur agit l inverse marche arri re lorsqu il re oit le signal de r gulation uniquement pour AMEI 6 iNET combin avec AFA 2 S1 DIP 4 S l...

Page 13: ...iretto o inverso fig 2 OFF l attuatore agisce direttamente sul segnale in ingresso ON l attuatore agisce in modo inverso sul segnale di comando solo per AMEI 6 iNET in combinazione con AFA 2 S1 DIP 4...

Page 14: ...0 mA 0 5 V 0 10 mA 5 10 V 10 20 mA S1 DIP 6 S1 DIP 5 0 10 V 2 10 V 0 10V 0 10 V 0 20 mA 2 10 V 2 10 V 4 20 mA S1 DIP 1 DIP 2 Y X S1 DIP 6 0 5 V 0 10 mA 5 10 V 10 20 mA S1 DIP 4 S1 DIP 7 S1 DIP 8 S2 S2...

Page 15: ...go lub przeciwnego kierunku dzia ania si ownika rys 2 WY Si ownik dzia a w kierunku zgodnym z sygna em wej ciowym W Si ownik dzia a odwrotnie odwrotnie w stosunku do sygna u steruj cego tylko dla AMEI...

Page 16: ...anies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved AMEi 6 Danfoss A S Heating Segment heating danfoss com 45 7488 2222 E Mail heating danfoss com 0 50 0 75 2 50 1...

Reviews: