AK-PC 772A
Capacity
controller RS8HF102 © Danfoss 2017-07
79
5. Check Analog outputs
6. Put the control of the output voltage back to auto-
matic
Press the
+
-button to go on to the next page
7. Check Analog inputs
Definition
Setting
0 %
50 %
100 %
0 - 10 V
0 V
5 V
10 V
1 - 10 V
1 V
5,5 V
10 V
0 - 5 V
0 V
2,5 V
5 V
2 - 5 V
2 V
3,5 V
5 V
Example of the connection between a defined output signal
and a manual set value.
Check that all sensors show sensible values.
In our case we have no values. This may be due to the following:
• The sensor has not been connected.
• The sensor is short-circuited.
• The point or module number has not been set up correctly.
• The configuration is not locked.
Set Control of output voltage to manual
Press in the
Mode
field.
Select
MAN
.
Press in the
Value
field
Select for example
50%
.
Press
OK
.
On the output you can now measure the expected value: In this
example 5 volts
Check of connections - continued