46
Capacity
controller RS8HF102 © Danfoss 2017-07
AK-PC 772A
Wiring
Decide during planning which function is to be connected and
where this will be.
1. Connect inputs and outputs
Here are the tables for the example:
Mounting and wiring - continued
The function of the switch functions can be seen in the last column.
There are pressure transmitters AKS 32R and AKS 2050 available for
several pressure ranges.
Here there are two different ones. One up to 59 bar and two up to 159
bar.
Remember the isolation amplifier
If signals are received from different controls, e.g. heat re-
covery for one of the inputs, a galvanically insulated module
should be inserted.
Signal
Module
Point
Terminal
Signal type /
Active at
1
1
(AI 1)
1 - 2
Shr container temperature
2
(AI 2)
3 - 4
Pt 1000
3
(AI 3)
5 - 6
Suction gas temperature - Ss MT
4
(AI 4)
7 - 8
Pt 1000
Discharge temperature - Sd MT
5
(AI 5)
9 - 10
Pt 1000
Suction pressure - P0 MT
6
(AI 6)
11 - 12
AKS 2050-59
Condensing pressure - Pc MT
7
(AI 7)
13 - 14
AKS 2050-159
8
(AI 8)
19 - 20
Suction gas temperature - Ss LT
9
(AI 9)
21 - 22
Pt 1000
Discharge temperature - Sd LT
10
(AI 10)
23 - 24
Pt 1000
Suction pressure - P0 LT
11
(AI 11)
25 - 26
AKS 2050-59
Compressor 1 MT
12
(DO 1)
31 - 32
ON
Compressor 2 MT
13
(DO 2)
33 - 34
ON
Compressor 3 MT
14
(DO 3)
35 - 36
ON
Compressor 1 LT
15
(DO 4)
37 - 38
ON
Compressor 2 LT
16
(DO 5)
39 - 40 - 41
ON
Valve and circulation pump HR
17
(DO6)
42 - 43 - 44
ON
Fan motors
18
(DO7)
45 - 46 - 47
ON
Hot gas dump
19
(DO8)
48 - 49 - 50
ON
24
-
25
-
Signal
Module
Point/Step
Terminal
Signal type
Compressor 1 MT Gen. Safety
2
1
(AI 1)
1 - 2
Open
Compressor 2 MT Gen. Safety
2
(AI 2)
3 - 4
Open
Compressor 3 MT Gen. Safety
3
(AI 3)
5 - 6
Open
All compressors common safety
MT
4
(AI 4)
7 - 8
Open
Compressor 1 LT Gen. Safety
5
(AI 5)
9 - 10
Open
Compressor 2 LT Gen. Safety
6
(AI 6)
11 - 12
Open
All compressors common safety LT
7
(AI 7)
13 - 14
Open
8
(AI 8)
15 - 16
Stepper signal to by-pass valve,
CCM
9 (step 1)
25 - 26 - 27 - 28
CCM (ETS)
10 (step 2)
29 - 30 - 31 - 32
Stepper signal to high pressure
valve, CCMT
11 (step 3)
33 - 34 - 35 - 36
CCMT
12 (step 4)
37 - 38 - 39 - 40
Signal
Module
Point
Terminal
Signal type
Outdoor temperature Sc3
3
1
(AI 1)
1 - 2
Pt 1000
Temp. gas cooler outlet Sgc
2
(AI 2)
3 - 4
Pt 1000
Gas cooler pressure Pgc
3
(AI 3)
5 - 6
AKS 2050-159
Receiver pressure Prec
4
(AI 4)
7 - 8
AKS 2050-159
Speed control, compressor MT
5
(AO 1)
9 - 10
0 - 10 V
Speed control, compressor LT
6
(AO 2)
11 - 12
0 - 10 V
Speed control, compressor, EC
7
(AO 3)
13 - 14
0 - 10 V
8
(AO 4)
15 - 16