© Danfoss | 2021.09 | 8

AQ37768222503601-000101 

AFQ 2 / VFQ 2(1) DN 15-125, VFQ 22(1) DN 65-250

ENGLISH

Safety Notes

Prior to assembly and commissioning 
to avoid injury of persons and damages 
of the devices, it is absolutely necessary 

to carefully read and observe these instructions.

Necessary assembly, start-up, and maintenance 
work must be performed only by qualified, 
trained and authorized personnel.

Prior to assembly and maintenance work on the 
controller, the system must be:

- depressurized,
-  cooled down,
-  emptied and
- cleaned.

Please comply with the instructions of the 
system manufacturer or system operator.

Definition of Application

The flow rate controller is used for flow rate 
restriction of water and water-glycol mixtures in 
heating, district heating and cooling systems.

The technical data on the label plates determine 
the use.

Scope of Delivery 

1)

 accessory sold separately, 

2)

 Impulse tube set - accessory sold separately 

Assembly

Admissible Installation Positions 

  media temperatures up to 15

0 °C: 

Can be installed in any positi on.

  media temperatures > 150 °C. 

Installation permitted only in horizontal 
pipelines with the actuator oriented 
downwards.

Installation Location and Installation 
Scheme 

Return mounting
Flow mounting

Valve Installation 

1.  Install strainer 

 before the controller.

2.  Rinse system prior to installing the valve.
3.  Observe flow direction 

 on valve body.

 Flanges 

 in the pipeline must be in 

parallel position and sealing surfaces 
must be clean and without any 
damage.

4.  Install valve.
5.  Tighten screws crosswise in 3 steps up to the 

max. torque.

Actuator Installation 

 The actuator stem must be screwed 
into the valve stem. Spring on the 
pressure actuator is factory adjusted 
(released) for proper installation.

1.  Remove the spindle protection cup and 

release the valve spindle by removing the 
nut, washer and cardboard tube.

2.  Align the actuator stem with the valve stem, 

connect both stems and turn gently the 
whole pressure actuator clockwise with both 
hands, until the stems are fully connected 
(valve stem fully screwed into the actuator 
stem). 

3.  Release the uninon nut by pulling out the 

blocking spring.

4.  Tight the union nut
5.  Release the pressure actuator by turning it 

counter clockwise for approximately half a 
turn.

6.  Observe the position of impulse tubes 

connection to the valve and align the 
actuator accordingly.

7.  Hold the actuator in the position and tight 

the union nut to the valve with 100- 120 Nm 
torque.

Impulse Tube mounting 

Connection of impulse tubes in the system - 
Overview

1. Installation in return flow 

2. Installation in supply flow 

.

Connection of impulse tube set 

Remove plug 

 at the valve.

Screw in threaded joint 

 with copper

seal. Torque: 40 Nm

For instalation of impulse tube sets, 
please observe the Installation 
Instructions for the Impulse tube sets.

Connection of impulse tube set AF

If control lines (copper) are not pre-bent or seal 
pots are to be installed, please observe the 
Assembly Instructions of these parts.

• Which impulse tubes to use?
The impulse tube set AF (2×) 

 

 can be used:

Order No.: 003G1391 or use the following pipes:

Stainless steel

Ø 10×0.8

DIN 17458, DIN 2391

Steel

Ø 10×1

DIN 2391

Copper

Ø 10×1

DIN 1754

Connection of impulse tube set 

❽①

1.  Cut pipe in rectangular sections 

 and 

deburr.

2.  For copper pipe: 

insert sockets 

 on both sides.

3.  Verify the correct position of the cutting 

ring 

.

4.  Press impulse tube 

 into the threaded joint 

up to its stop.

5.  Tighten union nut 

 Torque 40 Nm.

 When installing seal pots 

❽⑥

, please 

observe the Installati on Instructions 
for the seal pots.

Insulation 

For media temperatures up to 120 °C the 
pressure actua tor may be insulated 

.

Dismounting 

 

Danger

Danger of injury by hot water

Prior to dismounting depres surize system or 
use shut off valves on the impulse tubes! 

Carry out dismounting in following steps: 

1.   Fasten pressure actuator with the safety 

bands to the fixed points in surroundings 

2.  Before releasing the actuator, fully release 

the union nut

3.   Hold the pressure actuator with both 

hands, and release it by turning it counter 
clockwise ~30 turns. During turning, control 
the actuator weight all the time to prevent 
unexpected fall of detached actuator.

4.   Carefully remove the actuator from the valve.

Before installing actuator back to the valve, 
setting spring must be fully released again.

Leak and Pressure Test 

  "Danger of injury by heavy weight of 

pressure actuator. When dismounting 
the pressure actuator from the valve,

 control the actuator weight all the time to 
prevent unexpected fall of detached actuator 
and potential injuries due to the heavy weight!" 
To prevent damages  on the diaphragm 
pressure must be constantly and simultaneously 
increased at the + and − connection 

① 

until the 

max testing pressure is reached.

In case of higher test pressu res, remove impulse 
tubes 

 and close the valve with appropriate 

plugs.

Observe nominal pressure 

 of the valve.

Max. test pres sure must not exceed the plant 
testing pressure and must always be lower than  
1.5 × PN

Non-compliance may cause damages at the 
actuator or valve.

Filling the System, Start-up 

 The return flow pressure 

 must not 

exceed the supply flow pressure 

.

Non-compliance may cause damages at the 
controller 

.

1.  Slowly open valves in the system.
2.  Slowly open shut-off devices 

 in the supply 

flow.

3.  Slowly open shut-off devices 

 in the return 

flow.

Putting out of Operation

1.  Slowly close shut-off devices 

 in the supply 

flow.

2.  Slowly close shut-off devices 

 in the return 

flow.

Adjustment of Flow Rate Limitation

The flow rate is limited by adjusting the stroke of 
the adjusting throttle 

⓭①

.

There are two options:
1. Adjustment with the flow adjusting curves 
2. Adjustment with heat meter.

Adjustment with flow adjusting curves

The system must not be running!

When closing the adjusting throttle 
(step 3), the actuator could be damaged 
in case of high pressure differences. 

1.  Screw in adjusting throttle 

⓭②

 up to its 

stop.

 Valve is closed, no flow.

Summary of Contents for AFQ 2

Page 1: ...250 www danfoss com Seite 9 FRAN AIS AFQ 2 VFQ 2 1 DN 15 125 VFQ 22 1 DN 65 250 www danfoss com Page 10 ITALIANO AFQ 2 VFQ 2 1 DN 15 125 VFQ 22 1 DN 65 250 www danfoss com Pagina 12 AFQ 2 VFQ 2 1 DN...

Page 2: ...MAINTENANCE FREE 3 mm SW13 19 36 46 AF 2 2 DN 15 125 Tmax 150 C Bellows VFQ 2 AFQ 2 adapter 003G17801 Chamber VFQ 22 1 DN 65 250 Tmax 150 C AFQ 2 AF 1 2 Tmax 150 C VFQ 22 VFQ 2 21 DN 15 125 Tmax 150...

Page 3: ...N 65 250 Indirectly connected heating system Direct connected heating system Indirectly connected heating system Direct connected heating system SW46 Max 100 120 Nm 30 turns Pull out Hold Fix Release...

Page 4: ...AQ37768222503601 000101 4 Danfoss 2021 09 AFQ 2 VFQ 2 1 DN 15 125 VFQ 22 1 DN 65 250 T 150 C SW 19 40 Nm 30 Turns 30 Turns T 120 C T 120 C G 1 4 AF AFQ 2 VFQ 22 1 DN 65 250 SW 19 40 Nm SW 13...

Page 5: ...Danfoss 2021 09 5 AQ37768222503601 000101 AFQ 2 VFQ 2 1 DN 15 125 VFQ 22 1 DN 65 250 EN GJL 250 GG 25 PN 16 PN 25 EN GJS 400 GGG 40 3 PN 40 EN GP 240 GH GS C 25 SW 10 SW 10...

Page 6: ...3 4 5 6 7 8 9 10 11 12 13 flow m 3 h No of revolutions DN 100 p b 0 2 bar p b 0 5 bar 0 20 40 60 80 100 120 140 160 180 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 flow m 3 h No of revolutions DN 125 p b 0...

Page 7: ...3 239 239 241 241 H 267 267 304 304 323 323 Size A HA Weight cm2 mm kg 160 230 200 13 5 320 300 200 20 5 Total installation height of the controller VFQ 22 1 valve AFQ 2 pressure actuator is sum of HV...

Page 8: ...lse tube set AF If control lines copper are not pre bent or seal pots are to be installed please observe the Assembly Instructions of these parts Which impulse tubes to use The impulse tube set AF 2 c...

Page 9: ...u im R cklauf Einbau im Vorlauf Einbau des Ventils 1 Schmutzf nger vor dem Regler einbauen 2 Anlage vor dem Einbau des Ventils sp len 3 Flussrichtung auf dem Ventilgeh use beachten Flansche inderRohrl...

Page 10: ...eits und Druckpr fung Verletzungsgefahrdurchdashohe GewichtdesDruckantriebs Beider DemontagedesDruckantriebsvom VentilmussdieseraufgrunddeshohenGewichts kontinuierlich berwachtwerden umein unbeabsicht...

Page 11: ...eux mains et le rel cher en le tournant d environ 30 tours dans le sens inverse des aiguilles d une montre Pendant la rotation contr ler en permanence le poids de l actionneur pour viter sa chute inat...

Page 12: ...nstallazione dell attuatore Lostelodell attuatoredeveessere avvitatonellostelodellavalvola La mollasull attuatoredipressione regolatainfabbrica rilasciata per unacorrettainstallazione 1 Rimuovere il c...

Page 13: ...i mandata 3 Aprire lentamente i dispositivi di intercettazione nella portata di ritorno Messa fuori servizio 1 Chiudere lentamente i dispositivi di intercettazione nella portata di mandata 2 Chiudere...

Page 14: ...DN 15 125 VFQ 22 1 DN 65 250 40 Nm AF AF 2 003G1391 10 0 8 DIN 17458 DIN 2391 10 1 DIN 2391 10 1 DIN 1754 1 2 3 4 5 40 Nm 120 C 1 2 3 30 4 1 5 PN 1 2 3 1 2 1 2 3 1 2 3 4 p pmin 2 pb 1 2 3 1 8 DIN 2501...

Page 15: ...voln na prospr vnouinstalaci 1 Demontujte ochrann kryt v etena a uvoln te v eteno ventilu odstran n m matice podlo ky a lepenkov trubi ky 2 Vyrovnejte v eteno pohonu s d kem ventilu spojte oba d ky a...

Page 16: ...ta dozwolony wy cznie na ruroci gach poziomych z si ownikiem skierowanym w d Miejsce i schemat monta u Monta na ruroci gu powrotnym Monta na ruroci gu zasilaj cym Monta zaworu 1 Przed regulatorem zain...

Page 17: ...i nieniowy obiema r kami i zwolni go obracaj c w lewo o oko o 30 obrot w Podczas obracania przez ca y czas kontrolowa ci ar si ownika aby zapobiec jego nieoczekiwanemu upuszczeniu 4 Ostro nie zdj si o...

Page 18: ...2 40 AF AF 2 003G1391 10 0 8 DIN 17458 DIN 2391 10 1 DIN 2391 10 1 DIN 1754 Zbyt niski przep yw co zrobi Rozwi zanie 1 Sprawdzi regulacj patrz poprzednia sekcja 2 Sprawdzi r nic ci nie na zaworze regu...

Page 19: ...2021 09 19 AQ37768222503601 000101 AFQ 2 VFQ 2 1 DN 15 125 VFQ 22 1 DN 65 250 1 2 3 4 5 40 120 C 1 2 3 30 4 1 5 PN 1 2 3 1 2 1 2 3 1 2 3 4 p p 2 pb 1 2 3 1 8 DIN 2501 C 1 2 p pb p 0 2 V kVS 2 0 5 pb V...

Page 20: ...73695680 AQ37768222503601 000101 20 Danfoss DCS S SI 2021 09 AFQ 2 VFQ 2 1 DN 15 125 VFQ 22 1 DN 65 250 UA 15 15 6 04080...

Reviews: