Installation Guide 

AFP/VFG 2(21) DN 15-250

DEN-SMT/SI 

VI.CA.K2.1I 

District Energy 

LANGUAGE

ENGLISH

Safety Notes

Prior to assembly and commissioning to 

avoid injury of persons and damages of 

the devices, it is absolutely necessary to 

carefully read and observe these instructions.

Necessary assembly, start-up, and maintenance 

work must be performed only by qualified, 

trained and authorized personnel.

Prior to assembly and maintenance work on the 

controller, the system must be:

- depressurized,

-  cooled down,

-  emptied and

- cleaned.

Please comply with the instructions of the 

system manufacturer or system operator.

Disposal instructions

This product should be 
dismantled and its components 
sorted, if possible, in various 
groups before recycling or 
disposal.  

Always follow the local disposal regulations.

Definition of Application

The controller is used for diffe rential pressure 

control of water and water glycol mixtures for 

heating, district heating and cooling systems.

The technical data on the ra ting plates 

determine the use.

Scope of Delivery 

*)  Impulse tube AF, accessory

Assembly

Admissible Installation Positions 

DN 15-80 

:  

medium temperatures up to 120 °C: 

Can be installed in any positi on.

DN 100-250 and DN 15-80 

medium temperatures > 120 °C. 

Installation permitted only in horizontal 

pipelines with the actuator oriented 

downwards.

Installation Location and Installation 

Scheme 

Return mounting 

Flow mounting 

Valve Installation 

1.  Install strainer 

 before the controller.

2.  Rinse system prior to installing the valve.

3.  Observe flow direction 

 on valve body.

Flanges 

 in the pipeline must be in 

parallel position and sealing surfaces 
must be clean and without any damage.

4.  Install valve.

5.  Tighten screws crosswise in 3 steps up to the 

max. torque.

Valve Actuator Installation

Valves DN 150-250

The actuator stem must be screwed into 
the valve stem.

Observe the Installation In structions for the 

valves DN 150-250.

Valves DN 15-125 

1.  Place actuator at the valve.

2.  Align actuator, observe position of impulse 

tube connection to the valve 

3.  Tighten union nut 

 Torque 100 Nm

Impulse Tube mounting

When installing seal pots 

❻①

, please 

observe the Installati on Instructions for 
the seal pots.

•  Which impulse tubes to use?

 

The impulse tube set AF (2×) 

❻②

 can be 

used: Order No.: 003G1391

 

or use the following pipes: 

Stainless steel

Ø 10×0,8

DIN 17458,

DIN 2391

Steel

Ø 10×1

DIN 2391

Copper

Ø 10×1

DIN 1754

•  Connection 

 of impulse tubes 

 in the 

system

 

Installation in return flow 

 

Installation in supply flow 

•  Connection 

 to the pipeline 

 

No connection downwards 

, could be 

chocked by dirt.

•  Impulse Tube Installation (Copper) 

1.  Cut pipe into rectangular sections 

 and 

deburr.

2.  Insert sleeves 

 on both sides.

3.  Verify the correct position of the cutting 

ring 

.

4.  Press impulse tube 

 into the threaded 

joint up to its stop.

5.  Tighten union nut 

. Torque 40 Nm

Insulation 

For medium temperatures up to 100 °C the 

pressure actua tor may be insulated 

.

Dimensions 

Flanges:  connection dimensi ons acc. to 
 

DIN 2501, seal form C

Dismounting 

Danger

 

Danger of injury by hot water

Valve without actuator is open 

, Seal 

 is in 

the  ac tuator.

Prior to dismounting depres surize system!

Carry out dismounting in re verse order to 

mounting.

Leak and Pressure Test 

Pressure must be constantly increased 
at the +/-  connec tion 

. Never increase 

− pressure above + pressure.

Observe max. permitted pressure, see below. 

Non-compliance may cause damages at the 

actuator or valve.

Max. test pressure [bar] with connected 

impulse  tu bes

AFP cm

2

80

250

630

bar

25

25

16

In case of higher test pressu res, remove impulse 

tubes at the pipelines 

.

Close connections with plugs G ¼ ISO 228.

Observe nominal pressure 

 of the valve.

Max. test pres sure is 1,5 × PN

Filling the System, Start-up 

 

The return flow pressure 

 must not 

exceed the supply flow pressure 

.

Non-compliance may cause damages at the 

controller 

.

1.  Open shut-off devices 

 that are possibly 

available at the impulse tubes.

2.  Slowly open valves in the system.

3.  Slowly open shut-off devices 

 in the 

supply flow.

4.  Slowly open shut-off devices 

 in the return 

flow.

Putting out of Operation

1.  Slowly close shut-off devices 

 in the supply 

flow.

2.  Slowly close shut-off devices 

 in the return 

flow.

Differential Pressure Setting 

Set-point range see rating plate 

1.  Start-up of system, see section 

.

2.  Set flow rate on a motorised valve 

 by 

which the differential pressure is controlled, 

to about 50 % 

3. Adjustment

•  Observe pressure indica tors 

.

•  Turning to the right 

 increases the  set-

point (stressing the spring)

•  Turning to the left 

 redu ces the  

set-point (unstressing the spring)

4.  The set-point adjuster 

 may be sealed.

Summary of Contents for AFP Series

Page 1: ...e Page 9 FRANCAIS R gulateur de pression diff rentielle AFP VFG 2 21 www danfoss fr Page 10 ESKY Regul toru diferen n ho tlaku AFP VFG 2 21 www danfoss cz Page 11 SPANISH Controlador de presi n difere...

Page 2: ...250 tmax 140 C DN 15 125 tmax 150 C VFG 2 21 AFP AF 2 DN 15 125 tmax 200 C DN 150 250 tmax 200 C AFP 2 VFG 2 V1 V2 AF 2 2 2 Installation Guide AFP VFG 2 21 DN 15 250 District Energy VI CA K2 1I DEN S...

Page 3: ...3 3 Installation Guide AFP VFG 2 21 DN 15 250 District Energy VI CA K2 1I DEN SMT SI G 1 4 AF...

Page 4: ...150 238 9 25 160 238 10 32 180 240 13 40 200 240 17 50 230 275 22 65 290 275 33 80 310 380 41 100 350 380 60 125 400 380 79 150 480 326 85 200 600 354 145 250 730 404 228 VFG 2 tmax 200 C DN B1 L Weig...

Page 5: ...5 5 Installation Guide AFP VFG 2 21 DN 15 250 District Energy VI CA K2 1I DEN SMT SI ps 0 5 3 bar p 0 5 0 V x a m 36 mm...

Page 6: ...ots Which impulse tubes to use The impulse tube set AF 2 can be used Order No 003G1391 or use the following pipes Stainless steel 10 0 8 DIN 17458 DIN 2391 Steel 10 1 DIN 2391 Copper 10 1 DIN 1754 Con...

Page 7: ...mpepotte Valg af impulsledning Impulsledning s t AF 2 kan anvendes Best nr 003G1391 Hvis der anvendes andre typer skal f lgende v re opfyldt Rustfast St l 10 0 8 DIN 17458 DIN 2391 St l 10 1 DIN 2391...

Page 8: ...gen verwenden Steuerleitungsset AF 2 Bestellnummer 003G1391 oder folgende Rohre verwenden Edelstahl 10 0 8 DIN 17458 DIN 2391 Stahl 10 1 DIN 2391 Kupfer 10 1 DIN 1754 Anschluss der Steuerleitungen in...

Page 9: ...sset AF 2 kan anv ndas Best llningsnummer 003G1391 Om andra impulsledningar anv nds kontrollera f ljande dimensioner Rostfritt st l 10 0 8 DIN 17458 DIN 2391 St l 10 1 DIN 2391 Koppar 10 1 DIN 1754 An...

Page 10: ...res conduites utiliser les dimensions suivantes Tuyauterie Acier inox 10 0 8 DIN 17458 DIN 2391 Acier 10 1 DIN 2391 Cuivre 10 1 DIN 1754 Raccordement des conduites de commande dans l installation Mont...

Page 11: ...mont i Jak impulzn veden pou t Lze pou t impulzn veden AF 2 obj slo 003G1391 P i pou it jin ho veden respektujte n sleduj c rozm ry Trubka Nerezov ocel 10 0 8 DIN 17458 DIN 2391 Ocel 10 1 DIN 2391 M...

Page 12: ...Que tubo de impulsi n utilizar Puede utilizarse el kit AF 2x C digo 003G1391 O utilizar las tuber as siguientes Ac Inox 10 0 8 DIN 17458 DIN 2391 Acero 10 1 DIN 2391 Cobre 10 1 DIN 1754 Conexi n del t...

Page 13: ...Tilausnro 003G1391 Muita johtoja k ytett ess on huomioitava seuraavat mitat Ruostumaton ter s 10 0 8 DIN 17458 DIN 2391 Ter s 10 1 DIN 2391 Kupari 10 1 DIN 1754 Impulssijohtojen liitt minen j rjestelm...

Page 14: ...ane s inne rurki nale y zwr ci uwag na nast puj ce wymiary Stal nierdzewna 10 0 8 DIN 17458 DIN 2391 Stal 10 1 DIN 2391 Mied 10 1 DIN 1754 Pod czenie przewod w impulsowych w uk adzie Monta na ruroci g...

Page 15: ...ac se folosesc alte tuburi de impuls respecta i urm toarele dimensiuni O el inox 10 0 8 DIN 17458 DIN 2391 O el 10 1 DIN 2391 Cupru 10 1 DIN 1754 Montarea tuburilor de impuls n sistem Instalare pe con...

Page 16: ...sz m 003G1391 vagy haszn lja az al bbi vezet keket Rozsdamentes ac l tm r 10 0 8 DIN 17458 DIN 2391 Ac l tm r 10 1 DIN 2391 R z tm r 10 1 DIN 1754 Az impulzusvezet k csatlakoztat sa a rendszerhez Bek...

Page 17: ...trict Energy VI CA K2 1I DEN SMT SI 15 80 120 100 250 15 80 120 1 2 3 4 5 150 250 150 250 150 250 15 125 1 2 3 100 AF 2 003G1391 10 0 8 DIN 17458 DIN 2391 10 1 DIN 2391 10 1 DIN 1754 1 2 3 4 5 40 100...

Page 18: ...18 1 2 3 4 1 2 1 2 50 3 4 Installation Guide AFP VFG 2 21 DN 15 250 DEN SMT SI VI CA K2 1I District Energy...

Page 19: ...19 19 Installation Guide AFP VFG 2 21 DN 15 250 District Energy VI CA K2 1I DEN SMT SI...

Page 20: ...Installation Guide AFP VFG 2 21 DN 15 250 Produced by Danfoss A S 06 2013 73696440 VI CA K2 1I...

Reviews: