U•V6
Instruction Manual
19
|
65
Certified
ISO9001 • VCA
Standard Factory Settings
The
PEN01
configuration
is active on the U•V6 unit when it leaves the factory and is
delivered:
PEN01
F
R1 R2 R3 R4 R5
FAULT
Channel #
Target gas
& range
Power
Failure
Channel 1
CO 300ppm
A1
A2
A3
-
Channel 2
CO 300ppm
A1
A2
A3
-
Channel 3
CO 300ppm
A1
A2
A3
-
Channel 4
CO 300ppm
A1
A2
A3
-
Channel 5
CO 300ppm
A1
A2
A3
-
Channel 6
CO 300ppm
A1
A2
A3
-
A1, A2 and A3
represent the respective alarm conditions for each input channel.
F, R1, R2, R3, R4 and R5
represent the fault relay and the five alarm relays that can be
addressed.
A
symbol with an intersecting row and column indicates that the alarm condition in the
row, if met, will activate the relay in the corresponding column.
Configuration description:
▪
The six detector input channels are configured to detect CO with a range of
measurement of 300 ppm
▪
Single zone: identical alarm conditions all address the same relay
▪
The five programmable relays are addressed as follows:
o
Relays 1 & 2 are addressed to level-one alarms on the six input channels
o
Relays 3 & 4 are addressed to level-two alarms on the six input channels
o
Relay 5 is addressed to level-three alarms on the six input channels
▪
The fault relay works in failsafe mode
▪
The alarm relays are configured in non-failsafe mode