Instruction Manual
26
|
65
Certified
ISO9001 • VCA
Alarm relay 3
Not activated
Alarm Relay 3
Alarm relay 4
Not activated
Alarm Relay 4
Alarm relay 5
Not activated
Alarm Relay 5
Siren output
Not activated
Transistorised output for the siren
The user can confirm their selection by pressing
ENTER
. The system then asks for
confirmation before switching the output.
General fault relay
Ready to activate?
The user can confirm the activation of the selected output by pressing
ENTER
. It is then
activated, along with the equipment that is connected to it.
General fault relay
Activated
The output remains activated for the duration of the output test.
This comes to an end:
▪
upon manual action by user (pressing the
ESC
key).
▪
when the maximum activation time for the output (15 minutes) has expired.
The user may interrupt and cancel the
Output Test
function at any time by pressing
ESC
button
. The tests sub-menu is then re-enabled and displays the output test function.
Simulating a Detector
Navigation :
Service menu
→
Tests menu
→
Sensor simulation
A gas-detection simulation can be carried out without disconnecting a detector that is
connected to a measurement channel on the U•V6 unit.
Once the function has been selected, the user must select the detector for which the
simulation should be carried out.
The simulation starts when the detector has been selected: