CONFIGURATION
The configuration for the U•V6 unit comprises a set of menus that allows the system settings
to be configured. The user can access these menus, regardless of the s
tatus of the U•V6
unit, by pressing
ENTER
on the keyboard (if the display is in standby, the user should first
exit standby mode by pressing any key). Once in this mode, the display backlighting
turns
blue
.
The U•V6 unit automatically exits configuration mode after an idle period of 60 seconds (a
period in which no action is performed using the keyboard) and returns to the appropriate
mode: normal mode, if no faults or alarms have been signalled; fault mode, if a fault, but no
alarms, have been signalled; or alarm mode if an alarm has been signalled.
3.1
Unit-Configuration Principle
The factory settings for the U•V6 unit are intended for underground car parks and may be
changed depending on the intended use.
All the channels are deactivated in the factory. A detector-detection script must be run, so
that all the channels to which detectors have been connected can be activated (see
Paragraph 5.4.3 Spotting the Detectors
A gas-
detection system controlled by the U•V6 unit must be configured as follows:
1.
Detect the detectors and activate the input channels
2.
Select the appropriate "standard config."
3.
[Optional]
Select the target gases and alarm thresholds for each input channel
4.
[Optional]
Adjust the settings specific to the installation.
3.2
Addressing the Relays
Relay addressing involves connecting the alarm conditions configured with actions to open
or close contacts on the alarm relays. Depending on the requirements of the installation, a
standard configuration can be selected and, as a result, the appropriate devices can be
activated in the event of a gas detection.
These standard configurations come as presets, which are stored in the unit's memory. A
technician, who has been trained and certified by
Dalemans
, can activate the most
appropriate standard configuration for the installation during commissioning.
These operations require the intervention of qualified technicians. Contact
DALEMANS
for more information.
The PENxx standard configurations have been designed in accordance with EN 50545-1.
However, any subsequent modification may impact compliance with this standard. Please
contact your
DALEMANS
representative for more information.