SOFTWARE 

CONNECTION NIKY 600/800 Plus

The UPS is equipped with a USB interface, thanks to which it is possible by
means of a computer to access a set of data regarding the operation of the
UPS and control the operating system unattended shutdown.
Software is available as on option for Win98/ME/2000, Novell and Linux,
from the website www.daker.com without charge.
User license is included in the product.

TELEPHONE PROTECTION

The NIKY UPS has an integrated, standard RJ11/RJ45 passing telephone
connectionthat provides protection for telephone or network equipment
(modem, telephones, etc.) against overvoltage.

CHANGING BATTERIES

CAUTION

Opening, repairing, or replacing parts inside the UPS must always be carried
out by specialized technical personnel only.
First of all, switch off the UPS with the ON/OFF button located on the front
panel, then unplug the power cable from the 230V outlet socket. 

1) Switch off the uninterruptible power supply.
2) Unplug the power cable from the mains socket.
3) Change the batteries with others of the same type and make, or having
the same features

Keep clear from fire to avoid explosion while handling batteries.
Do not open or tamper with the battery case, because it contains toxic
electrolyte that could be harmful for your skin or eyes. Keep out of children’s
reach.

NOTICE

The batteries must only be replaced by qualified technical personnel, who will
dispose of them in compliance with the law in force.

POSSIBLE MALFUNCTIONING

The UPS always operates on batteries:

There is no line voltage

Line voltage is out of allowed UPS range

The power supply cable is not correctly connected to mains socket.

The input circuit breaker has to be reset

The mains socket is defective

The UPS signals overloading:

Additional loads to the ones normally connected have involuntarily been

connected on the output line.

Check all the loads connected to the output

The UPS doesn’t operate in battery mode (it shuts down or immediately 
signals it is close to the operating limit):

The UPS has operated with no mains voltage for a long time and has not

been able to recharge the battery. Recharge it for at least 6 hours by
connecting the uninterruptible power supply to the mains.

The battery is flat due to not using the UPS for a long period. Recharge it

for at least 6 hours by connecting the uninterruptible power supply to the
mains.

The battery has run down due to being used frequently, to ambient

conditions, or to having exceeded its average service life; it is necessary
to change it.

The UPS doesn’t deliver power to the output:

Check that the loads are correctly connected to the output sockets  

TECHNICAL FEATURES

Construction Specifications 

Weights 
Dimensions L x H x P in mm
Protection

Ambient specifications

Operating temperature range
Operating relative humidity range
Degree of protection as per IEC529
Noise level at 1 meter

< 40 dBA

Electrical input specifications

Rated input voltage

230 V

Range of input voltage 

from 160 V to 290 V

Rated input frequency

50 or 60 Hz ± 1 Hz

Maximum input current 
Number of input phases  

Single phase

Waveform on output

With battery operation 
Type of operation 

Electrical specifications on output

Rated output voltage
Output current on nominal load
Apparent output capacity on nominal load
Apparent output capacity on nominal load
Overload capacity 

110% for 5 s.

Number of phases on output

600 VA

300 W

2,6 Arms

3,75 Arms

from 0 to +40 °C

from 0 to 90% non-condensing

step wave

line interactive

Single phase

IP20

95 X 171 X 354

Electronic protection against overloading and short-circuiting    

Shutdown on reaching operating limit and overheating.

Automatic shutdown due to protection triggering

7 Kg.

600

800 Plus

MetaSystem reserves to itself the right to modify the above specified data
without previous notice.

©Copyright by MetaSystem SpA 

The batteries are considered hazardous waste and should be disposed of
in accordance with current regulations.

Electrical specifications on output with battery operation

Rated output voltage

230 V ± 10%

Output frequency 
Active output capacity on non-linear load

Apparent output capacity on 
non-linear load 

Battery operation

Operating time (with batteries charged)
with a PC load + 15” monitor

Charging time 
Technical data and number of batteries

Standards

Electromagnetic compatibility
Emission - Immunity
Safety
Performance and features

n°1 maintenance-free,

sealed, lead-acid

battery 12V 7,2 Ah

50/60 Hz ± 1Hz

10/12 h at the end of operating range

Conforms to  EN 50091 - 2

Conforms to EN 62040 -1 -1

Conforms to EN 62040 - 3

300 W

35 min.

600 VA

n° 1

maintanance-

free, lead-acid,

sealed 12V 9 Ah 

800 VA

400 W

3,48 Arms

5 Arms

7,5 Kg.

400 W

800 VA

230 V ± 10 %

40 min.

Summary of Contents for Niky 600

Page 1: ...ausa della loro elevata corrente di spunto Non usare l UPS per alimentare elettrodomestici quali asciugacapelli condizionatori frigoriferi ecc IT Direttore Tecnico INSTALLAZIONE Estrarre l UPS dall imballo Assicurarsi che la tensione di rete dell impianto sia uguale a quella riportata sull etichetta apposta sul retro dell UPS Accendere l UPS tramite il pulsante ON OFF e verificarne il normale funz...

Page 2: ...RJ45 passante che consente di proteggere gli apparati telefonici modem telefoni ecc e di rete dalle sovratensioni SOSTITUZIONE E MANUTENZIONE DELLE BATTERIE AVVERTENZA L apertura la riparazione o la sostituzione di parti all interno dell UPS richiede sempre l intervento di personale tecnico specializzato Prima di ogni intervento spegnere l UPS agendo sul pulsante ON OFF posto sul frontale quindi d...

Page 3: ...and where it is not too damp Do not place near equipments that generate strong electro magnetic fields and or near equipments that are sensible to electro magnetic fields engines floppy disks speakers adapters monitors video etc Do not pour any liquid on the UPS or inside the UPS Do not place the UPS in humid environment or near liquid such as water chemical solution Do not expose the UPS to the d...

Page 4: ...ot using the UPS for a long period Recharge it for at least 6 hours by connecting the uninterruptible power supply to the mains The battery has run down due to being used frequently to ambient conditions or to having exceeded its average service life it is necessary to change it The UPS doesn t deliver power to the output Check that the loads are correctly connected to the output sockets TECHNICAL...

Page 5: ...der Verpackung Vergewissern Sie sich dass die Netzspannung der Anlage mit derjenigen auf dem Etikett angegebenen angebracht auf der Rückseite der USV übereinstimmt Schalten Sie die USV mittels der Taste ON OFF ein und prüfen Sie damit den normalen Netzbetrieb das grüne LED leuchtet Schalten Sie die USV ab indem Sie die Taste ON OFF bis zur Abschaltung des LEDs gedrückt halten Nachdem Sie die USV a...

Page 6: ...en Lasten Die USV funktioniert im Batteriebetrieb nicht die USV blockiert sich oder meldet sofort autonome Reserve Die USV war lange Zeit ohne Netzanschluss in Betrieb und hatte keine Möglichkeit die Batterie aufzuladen Laden Sie die Batterie für wenigstens 6 Stunden wieder auf indem Sie die eingeschaltete USV ans Netz anschließen Die Batterie ist aufgrund einer langen inaktiven Phase der USV entl...

Page 7: ...ÔÚÙ Ô ÛÙËÓ Û ÛΠÙÔ Ô Ô Ô ÂÚ ÓÂÈ ÙËÓ Ì ÁÈÛÙË Â ÈÙÚ fiÌÂÓË ÈÛ ÙË Ô UPS ÂÓ ÏÂÈÙÔ ÚÁ Û Π٠ÛÙ ÛË Ì Ù ÚÈÒÓ Û ÓÂÈ ÙfiÌ Ù Ó ÂÈ ÚÔÂÈ Ô ÔÈËÙÈÎ Ó ÂÈÍË ÌËÏ ÛÙ ıÌË Ì Ù Ú ñ Ú ÂÓ ÙÚÔÊÔ ÔÙ ÙËÓ Û ÛΠ̠ÚÂ Ì ÁÈ ÚÎÂÙfi È ÛÙËÌ Î È ÂÓ ÂÈ ÊÔÚÙÈÛÙÂ Ë Ì Ù Ú ñ Û ÛΠÂÓ ÂÈ ÚËÛÈÌÔ ÔÈËı ÁÈ ÚÎÂÙfi È ÛÙËÌ Î È Ë Ì Ù Ú ÚÂÈ ÂÙ È ÊfiÚÙÈÛË ñ Ì Ù Ú ÚÂÈ ÂÙ È ÓÙÈÎ Ù ÛÙ ÛË ÏfiÁÔ Ê ÛÈÎ ÊıÔÚ Ò Ó Â ı Óı Ù ÁÈ service È ÂÓ Â fiÌÂÓË Â ÈÛÎ...

Page 8: ... ÚfiÓÔ ÓÙÈÎ Ù ÛÙ ÛË ÙË Ì Ù Ú ÙË Û ÛÎÂ È Ê ÚÂÈ Ó ÏÔÁ Ì ÙËÓ Ú ÛË ÙË Î È ÙËÓ ÔÈfiÙËÙ ÚÂ Ì ÙÔ ÙÔ ÊÔÚ Â ÂÚ ÙˆÛË ÌË ÔÌ Ï ÏÂÈÙÔ ÚÁ ÙË Ì Ù Ú Ó ÂÈ Ë ÚÔÂÈ Ô ÔÈËÙÈk ÎfiÎÎÈÓË Ï Ó È Ó ÓÙÈÎ Ù ÛÙ ÛÂÙ ÙËÓ Ì Ù Ú ÙË Û ÛΠÎÏ ÛÙ ÙÔ È Îfi ÙË ÏÂÈÙÔ ÚÁ ÙÔ UPS Î È Ê ÈÚ ÛÙ ÙÔ Î ÏÒ ÈÔ ÚÂ Ì ÙÔ fi ÙËÓ Ú ÓÙÈÎ Ù ÛÙ ÛÙ ÙËÓ ÏÈ Ì Ù Ú ÌÂ Ó ÙÔ ÈÔ ÎÚÈ Ò Ù Ô ...

Page 9: ...corrosivas y en ambientes no excesivamente húmedos No se debe colocar cerca de aparatos que generen fuertes campos electromagnéticos y o de aparatos sensibles a los campos electromagnéticos motores unidades floppy disk altavoces transformadores monitores pantallas etc No se deben verter líquidos encima ni dentro del SAI Hay que evitar exponer el SAI a la luz directa del sol y no se debe situar cer...

Page 10: ... red La batería se ha agotado debido al uso frecuente a las condiciones ambientales o a que ha llegado al término de su vida útil es necesario cambiarla El SAI no proporciona tensión en salida o Comprobar que sea correcta la conexión de las cargas en las tomas de salida CARACTERÍSTICAS TÉCNICAS Las baterías son consideradas residuos peligrosos y deben ser eliminadas según las normas vigentes MetaS...

Page 11: ...ode ser utilizada antes das baterias estarem completamente descarregadas mas isto faz com que o tempo de autonomia à disposição em caso de black out seja mais breve 12 11 2008 SINALIZAÇÕES E COMANDOS Sinalizações luminosas A cor do LED colocado no painel dianteiro tem os seguintes significados LED verde fixo rede presente e regular carregamento das baterias LED verde intermitente cada 3 seg funcio...

Page 12: ...regulamentações em vigor A MetaSystem reserva se o direito de proceder sem comunicação prévia a variações às especificações acima indicadas Copyright by MetaSystem SpA C CARACTERÍSTICAS TÉCNICAS E Especificações construtivas 600 800 7 o s e P Kg 7 5 Kg 4 5 3 x 1 7 1 x 5 9 s o r t e m í l i m m e P x H x L s e õ s n e m i D Protecções E x e a r t n o C s a c i n ó r t c e l cessos de carga e curto ...

Page 13: ...n utilisant les prises situées dans la porte arrière de l UPS Allumer l UPS puis la charge pour vérifier son bon fonctionnement avec alimentation secteur led verte allumée Maintenir l UPS allumé pendant 8 heures avant de l utiliser afin de recharger les batteries L UPS peut être également utilisé avant que les batteries soient complètement chargées mais la durée d autonomie disponible en cas de bl...

Page 14: ...tion fréquente des conditions environnementales ou du dépassement de la durée moyenne de vie elle doit être remplacée L UPS ne fournit pas de tension en sortie vérifier que les charges sont correctement branchées aux prises de sortie Les batteries sont considérées comme des déchets dangereux et doivent être éliminées suivant la réglementation en vigueur MetaSystem se réserve le droit d apporter sa...

Page 15: ...dem o red informática PT Protection de telefone fax modem o rede FR Protection puor téléphone fax modem ou réseau I Uscite GB Output sockets D Ausgänge EL ŒÍÔ ÔÈ UPS ES Conector de salida PT Ficha de saída FR Sortíe I Presa di ingresso rete con fusibile GB AC Input with AC Fuse D Eingangssteckerbuchsen mit Schmelzsicherung EL ÛÔ Ô ƒÂ Ì ÙÔ ES Entrada AC con fusibile AC PT Ficha de entrada con fusív...

Reviews: