4.1 Choosing the best place

the detector must be placed:

• in rooms where there is a risk of fires

spreading quickly or at an average speed,

• in rooms with an aggressive or difficult

environment such as kitchens (cooking
fumes), garages (smoky atmosphere), and
other unoccupied premises or rooms where
there is often a lot of dust, 

• preferably at the centre of the ceiling but

positioned so that it is affected by any
abnormal rises in temperature,

• if the detector cannot be installed in the

centre of the ceiling, install it more than 50
cm away from the corners of the room (Fig.
1 and Fig. 2),

• far away from ventilation grilles that may

spread the heat,

• more than 50 cm away from obstacles

(walls, partitions, beams, etc.),

• at either end of corridors more than 8 m

long,

• far away from potential sources of electrical

interference (electricity meter, metal cabinet,
etc.),

• if it is to be installed on a metal wall, insert a

shim made of non-magnetic material (wood
or plastic).

the detector must not be placed:

• in rooms where a sudden and considerable

rise in the room temperature would cause
untimely triggering of the alarms (e.g.
sudden sunlight),

• in rooms where there is a need to protect

people against smoke or gas(bedrooms,
children’s playrooms, converted cellars,
occupied lofts, emergency exits, etc.),

• near fluorescent tubes,
• directly on a metal surface,
• in a room where the temperature could drop

below -10°C or rise above +55°C, as this
will prevent the detector from operating
properly,

4. Installing the detector

Make sure there is a distance of at least 2 m between each product, except between two

detectors.

iMPoRtAnt: the heat detector is not supposed to replace smoke or gas detectors to

ensure the safety of people against smoke or gas, and notably in rooms such as bedrooms,

playrooms and other living areas. the heat detector is designed to detect fires in places

where an optical smoke detector cannot be used. For basic protection, a smoke detector

should be installed in at least each bedroom (refer to smoke detector manual).

Summary of Contents for 155-21X

Page 1: ...Upgraded for e Nova applications...

Page 2: ...an abnormal speed or when the room temperature reaches between 54 C and 70 C also refer to the table in the Technical Data section The heat detector is especially suitable for detecting res that spre...

Page 3: ...r provided with this product Heat detector transmitting the heat detection signal other hard wired interconnected heat detectors the LED ashes quickly a built in modulated alarm sounds on a continuous...

Page 4: ...und The red LED ashes for 15 sec then once every 10 sec to indicate that the detector is working normally 2 Power supply 3 Recognition programming iMPoRtAnt during recognition programming the product...

Page 5: ...shim made of non magnetic material wood or plastic the detector must not be placed in rooms where a sudden and considerable rise in the room temperature would cause untimely triggering of the alarms...

Page 6: ...t if there is no voice message move the heat detector closer to the control panel le 2 Put the control panel back in user mode by pressing in rooms where the relative humidity might rise above 95 with...

Page 7: ...opriate plugs and screws Fixing with ush mounting box 1 For 60 mm diameter boxes use holes marked 2 For 85 mm diameter boxes use holes marked 3 Fix the base using suitable screws 60 85 60 85 optional...

Page 8: ...e g a 155 21X can be connected with 155 21X heat detectors or 151 21X smoke detectors For 15 mm2 wires the overall network length must not exceed 400 m 3 Clip the connector block back in place 4 Lock...

Page 9: ...perature measurement If the heat sensor is faulty the heat detector indicates that there is a technical fault see Indications section There is therefore no need to test the detector using a source of...

Page 10: ...lephone dialler Stop the sirens and check that the control panel has memorised the alarm see Indications section iMPoRtAnt these tests should be carried out at least once a month and notably when you...

Page 11: ...etector stops its built in sounding The LED indicating the status of the detector ashes every 2 sec Following the 15 min disable period the detector is automatically reset to normal operation with the...

Page 12: ...stem command the control panel issues the following voice message beep fault battery detector n X 7 Indications iMPoRtAnt in order not to wake you up audible alarms resulting from power problems or te...

Page 13: ...r head You should vacuum clean the detection head slots if there is a lot of dust in the room 8 Maintenance Heat detector transmitting the fault signal other hard wired interconnected heat detectors t...

Page 14: ...ent reliability Dispose of the waste lithium power pack in an appropriate recycling bin 8 2 Changing the battery if the optional opening of the detector is not locked see Fixing 1 Remove the detector...

Page 15: ...ctor status alerts triggered faults White LED safety lighting in case of detection Built in sounding 85 dB at 3 m in case of detection 75 dB at 3 m during testing or fault indication Hard wired interc...

Page 16: ...6 00 3 7 13 16 00 5 4 09 10 00 10 2 00 5 30 20 1 00 3 13 30 0 40 2 25 or depending on the temperature rise speed A2 class detector response time according to EN 54 5 chapter 5 4 3 Examples if the temp...

Page 17: ...the user Do not forget to remove the plastic cover when the work is finished Heat detection 1 All heat detectors the LED ashes once every 10 sec Red LeD indicating detector status White LeD Sounding H...

Page 18: ...l the rst beep sounds You should contact your installation engineer within this same period in order to rectify the problem Following the 15 min disable period the detector is automatically reset to n...

Page 19: ...95 eC in compliance with the following harmonised European standards This product can be used in all EU EEA Countries and Switzerland Crolles 02 01 2013 Signature Patrick Bernard Director of Research...

Page 20: ...2280612004 01 2013...

Reviews: