Field Setting
SiUS34-907
80
Test Operation
The numbers in the "No." column represent the number of times to press the SET
(BS2) button.
Setting item 0 Display contents of “Various setting”
No.
Setting item
LED display
Data display
H1P H2P H3P H4P H5P H6P H7P
0
Various setting
l h h h h h h
See below
1
C/H unified address
l h h h h h k
Lower 6 digits
2
Low noise/demand address
l h h h h k h
3
Not used
l h h h h k k
4
AIRNET address
l h h h k h h
5
Number of connected indoor units
l h h h k h k
7
Number of connected zone units
(excluding outdoor and BS unit)
l h h h k k k
8
Number of outdoor units
l h h k h h h
11
Number of zone units (excluding
outdoor and BS unit)
l h h k h k k
Lower 6 digits
12
Number of terminal blocks
l h h k k h h
Lower 4 digits: upper
13
Number of terminal blocks
l h h k k h k
Lower 4 digits: lower
14
Contents of malfunction (the
latest)
k h h k k k h
Malfunction code table
Refer to P.103.
15
Contents of malfunction
(1 cycle before)
k h h k k k k
16
Contents of malfunction
(2 cycle before)
k h k h h h h
20
Contents of retry (the latest)
k h k h k h h
21
Contents of retry (1 cycle before)
k h k h k h k
22
Contents of retry (2 cycle before)
k h k h k k h
25
Normal judgement of outdoor units
PCB
l h k k h h k
Lower 2 digits:
k h
Abnormal
h k
Normal
h h
Unjudgement
EMG operation /
backup operation
setting
ON
l h h k h h h
OFF
l h h h h h h
Defrost select setting
Short
l h h h k h h
Medium
l h h h l h h
Long
l h h h h h h
Te setting
H
l h h h h k h
M
l h h h h l h
L
l h h h h h h
Tc setting
H
l h h h h h k
M
l h h h h h l
L
l h h h h h h
c. Monitor mode
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns to “Setting mode 1”.
Summary of Contents for VRV III-S RXYMQ36 48PVJU
Page 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Page 9: ...SiUS34 907 Safety Considerations viii...
Page 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Page 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Page 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Page 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Page 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Page 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Page 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Page 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 247: ...Option List SiUS34 907 238 Appendix...
Page 249: ...Example of Connection 240...
Page 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...