Troubleshooting (OP: Unified ON/OFF Controller)
SiUS34-907
208
Troubleshooting
Is the
wiring adaptor for
electrical appendices
connected?
Schedule timer and parallel
interface cannot be used in
combination. Disconnect either
the schedule timer or parallel
interface and reset the power
supply for all optional controllers
for centralized control
simultaneously.
Is a parallel interface
connected?
Disconnect the schedule timer's
individual / combined connector
and reset the power supply for
all optional controllers for
centralized control
simultaneously.
YES
Is the
schedule timer's individual/
combined connector
connected?
YES
NO
A
Cannot be used in combination
with a wiring adaptor for
electrical appendices. Remove
the wiring adaptor for electrical
appendices and reset the power
supply for all optional controllers
for centralized control
simultaneously.
YES
Arrange so that the connector
for setting master controller is
connected to one controller for
centralized control and reset the
power supply for all optional
controllers for centralized
control simultaneously.
YES
NO
If the malfunction is still not cleared:
Is a schedule timer
connected?
Are
there two or more
optional controllers for
centralized control connected with
the connector for setting
master controller?
YES
NO
NO
NO
Reset the power supply for all optional
controllers for centralized control
simultaneously.
Disconnect the connector for
setting master controller from
the master controller, connect to
another optional controller for
centralized control and
simultaneously reset all optional
controllers for centralized
control again. The controller
connected by the connector for
setting master controller when
the malfunction is cleared is
defective and must be replaced.
Summary of Contents for VRV III-S RXYMQ36 48PVJU
Page 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Page 9: ...SiUS34 907 Safety Considerations viii...
Page 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Page 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Page 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Page 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Page 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Page 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Page 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Page 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 247: ...Option List SiUS34 907 238 Appendix...
Page 249: ...Example of Connection 240...
Page 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...