SiUS34-907
Specifications
Specifications
9
4 Way Ceiling Mounted Cassette Unit (2’×2’)
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB (27°CDB), 67°FWB (19.4°CWB)
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Outdoor temperature: 47°FDB (8.3°CDB), 43°FWB (6°FWB)
Equivalent ref. piping length: 25ft (7.5 m) (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
FXZQ07M7VJU
FXZQ09M7VJU
FXZQ12M7VJU
FXZQ18M7VJU
1 Cooling Capacity
Btu/h
7,500
9,500
12,000
18,000
2 Heating Capacity
Btu/h
8,700
11,100
14,000
21,000
Casing / Color
Galvanized Steel / Non
Painted
Galvanized Steel / Non
Painted
Galvanized Steel / Non
Painted
Galvanized Steel / Non
Painted
Dimensions: (H×W×D)
in. (mm)
10-1/4 (11-1/4) x 22-2/3 x 22-
2/3
(260 (286) x 576 x 576)
( ): includes Electrical
Componets Box
10-1/4 (11-1/4) x 22-2/3 x 22-
2/3
(260 (286) x 576 x 576)
( ): includes Electrical
Componets Box
10-1/4 (11-1/4) x 22-2/3 x
22-2/3
(260 (286) x 576 x 576)
( ): includes Electrical
Componets Box
10-1/4 (11-1/4) x 22-2/3 x 22-
2/3
(260 (286) x 576 x 576)
( ): includes Electrical
Componets Box
Coil (Cross
Fin Coil)
Rows×Stages×FPI
2
×
10
×
0.06
2
×
10
×
0.06
2
×
10
×
0.06
2
×
10
×
0.06
Face Area
ft²(m²)
2.9 (0.9)
2.9 (0.9)
2.9 (0.9)
2.9 (0.9)
Fan
Model
QST32C15M
QST32C15M
QST32C15M
QST32C15M
Type
Turbo Fan
Turbo Fan
Turbo Fan
Turbo Fan
Motor Output (High)
W
55
55
55
55
Airflow Rate (H/L)
cfm
320/247
335/265
495/353
320/247
Drive
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Air Filter
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Piping
Connections
Liquid Pipes
in. (mm)
φ
1/4(6.4)(Flare Connection)
φ
1/4(6.4) (Flare Connection)
φ
1/4(6.4) (Flare Connection)
φ
1/4(6.4) (Flare Connection)
Gas Pipes
in. (mm)
φ
1/2 (12.7) (Flare Connection)
φ
1/2(12.7) (Flare Connection)
φ
1/2(12.7)(Flare Connection)
φ
1/2(12.7)(Flare Connection)
Drain Pipe
in. (mm)
VP20
External Dia. 1.02 (26)
Internal Dia. 0.79 (20)
VP20
External Dia. 1.02 (26)
Internal Dia. 0.79 (20)
VP20
External Dia. 1.02 (26)
Internal Dia. 0.79 (20)
VP20
External Dia. 1.02 (26)
Internal Dia. 0.79 (20)
Machine Weight (Mass)
Lbs (kg)
42 (19)
42 (19)
42 (19)
42 (19)
4 Sound Level (H/L)
dBA
31/29
33/29
41/34
41/34
Safety Devices
Fuse
Fuse
Fuse
Fuse
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R-410A Series
R-410A Series
R-410A Series
R-410A Series
Decoration
Panels
(Option)
Model
BYFQ60BU
BYFQ60BU
BYFQ60BU
BYFQ60BU
Color
White (RAL 9010)
White (RAL 9010)
White (RAL 9010)
White (RAL 9010)
Dimensions: (H×W×D)
in. (mm)
2-1/4 x 27-1/2 x 27-1/2 (57 x
699 x 699)
2-1/4 x 27-1/2 x 27-1/2 (57 x
699 x 699)
2-1/4 x 27-1/2 x 27-1/2 (57 x
699 x 699)
2-1/4 x 27-1/2 x 27-1/2 (57 x
699 x 699)
Weight
Lbs (kg)
6 (2.7)
6 (2.7)
6 (2.7)
6 (2.7)
Standard Accessories
Installation and Operation
manual, Paper pattern for
installation, Drain hose,
Clamp metal, Washer fixing
plate, Sealing pads, Clamps,
Screws, Washer for hanger
bracket, Insulation for fitting.
Installation and Operation
manual, Paper pattern for
installation, Drain hose,
Clamp metal, Washer fixing
plate, Sealing pads, Clamps,
Screws, Washer for hanger
bracket, Insulation for fitting.
Installation and Operation
manual, Paper pattern for
installation, Drain hose,
Clamp metal, Washer fixing
plate, Sealing pads, Clamps,
Screws, Washer for hanger
bracket, Insulation for fitting.
Installation and Operation
manual, Paper pattern for
installation, Drain hose,
Clamp metal, Washer fixing
plate, Sealing pads, Clamps,
Screws, Washer for hanger
bracket, Insulation for fitting.
Drawing No.
C:3TW30721-1
(
)
(
)
(
)
(
)
Summary of Contents for VRV III-S RXYMQ36 48PVJU
Page 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Page 9: ...SiUS34 907 Safety Considerations viii...
Page 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Page 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Page 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Page 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Page 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Page 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Page 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Page 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 247: ...Option List SiUS34 907 238 Appendix...
Page 249: ...Example of Connection 240...
Page 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...