Troubleshooting by Indication on the Remote Controller
SiUS34-907
138
Troubleshooting
3.17
“
E7
”
Malfunction of Outdoor Unit Fan Motor
Remote
Controller
Display
E7
Applicable
Models
RXYMQ36 · 48PVJU
Method of
Malfunction
Detection
Detect a malfunction based on the current value in the inverter PCB (as for motor 2, current value in
the fan PCB).
Detect a malfunction for the fan motor circuit based on the number of rotation detected by hole IC
during the fan motor operation.
Malfunction
Decision
Conditions
Overcurrent is detected for inverter PCB (A2P) or fan inverter PCB (A3P)
(System down is caused by 4 times of detection.)
In the condition of fan motor rotation, the number of rotation is below the fixed number for more
than 6 seconds. (System down is caused by 4 times of detection.)
Supposed
Causes
Failure of fan motor
Defect or connect ion error of the connectors/ harness between the fan motor and PCB
The fan can not rotate due to any foreign substances entangled.
Clear condition: Continue normal operation for 5 minutes
Summary of Contents for VRV III-S RXYMQ36 48PVJU
Page 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Page 9: ...SiUS34 907 Safety Considerations viii...
Page 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Page 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Page 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Page 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Page 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Page 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Page 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Page 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 247: ...Option List SiUS34 907 238 Appendix...
Page 249: ...Example of Connection 240...
Page 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...