SiUS34-907
Refrigerant Circuit
Refrigerant Circuit
27
1. Refrigerant Circuit
1.1
RXYMQ36 · 48P
No. in
refrigerant
system
diagram
Symbol
Name
Major Function
A
M1C
Inverter compressor (INV.)
Inverter compressor is operated on frequencies between 36Hz and 195Hz by using the
inverter.
31 steps
D
M1F
M2F
Inverter fan
Because the system is of an air heat exchange type, the fan is operated at 8-step rotation
speed by using the inverter.
E
Y1E
Electronic expansion valve
(Main: EV1)
While in heating operation, PI control is applied to keep the outlet superheated degree of
air heat exchanger constant.
F
Y3E
Electronic expansion valve
(Subcooling: EV3)
Pl control is applied to keep the outlet superheated degree of subcooling heat exchanger
constant.
G
Y2S
Solenoid valve (Hot gas: SVP) Prevents the low pressure from transient falling.
H
Y3S
Solenoid valve (Unload circuit
SVUL)
Unloading operation of compressor.
M
Y1S
Four-way valve
Switches the operation mode between cooling and heating.
N
S1NPH High pressure sensor
Detects high pressure.
O
S1NPL
Low pressure sensor
Detects low pressure.
P
S1PH
High pressure switch (For
INV. compressor)
In order to prevent the increase of high pressure when a malfunction occurs, this switch is
activated at high pressure of 580psi or more to stop the compressor operation.
S
—
Fusible plug
In order to prevent the increase of pressure when abnormal heating is caused by fire or
others, the fusible part of the plug is molten at a temperature of 158 to 167°F to release
the pressure into the atmosphere.
T
—
Pressure regulating valve 1
(Receiver to discharge pipe)
This valve opens at a pressure of 580 psi for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in transportation
or storage.
1
R1T
Thermistor (Outdoor air: Ta)
Detects outdoor temperature, correct discharge pipe temperature, and others.
2
R2T
Thermistor (INV. discharge
pipe: Tdi)
Detects discharge pipe temperature, make the temperature protection control of
compressor, and others.
3
R3T
Thermistor
(Suction pipe1: Ts1)
Detects suction pipe temperature, keeps the suction superheated degree constant in
heating operation.
4
R4T
Thermistor (Heat exchanger
deicer: Tb)
Detects liquid pipe temperature of air heat exchanger, determine defrosting operation, and
others.
5
R5T
Thermistor
(Suction pipe2: Ts2)
Calculates internal temperature of compressor.
6
R6T
Thermistor (Subcooling heat
exchanger gas pipe: Tsh)
Detectst gas pipe temperature on the evaporation side of subcooling heat exchanger,
keep the superheated degree at the outlet of subcooling heat exchanger constant, and
others.
7
R7T
Thermistor
(Liquid pipe: Tl)
Detects liquid pipe temperature.
Summary of Contents for VRV III-S RXYMQ36 48PVJU
Page 1: ...RXYMQ36 48PVJU R 410A Heat Pump 60Hz SiUS34 907...
Page 9: ...SiUS34 907 Safety Considerations viii...
Page 237: ...Wiring Diagrams SiUS34 907 228 Appendix 2 2 Field Wiring RXYMQ36 48PVJU 3D065370...
Page 238: ...SiUS34 907 Wiring Diagrams Appendix 229 2 3 Indoor Unit FXFQ12M 18M 24M 30M 36MVJU 3D042620C...
Page 239: ...Wiring Diagrams SiUS34 907 230 Appendix FXZQ07M 09M 12M 18MVJU 3D059263...
Page 240: ...SiUS34 907 Wiring Diagrams Appendix 231 FXDQ07M 09M 12M 18M 24MVJU 3D050501A...
Page 241: ...Wiring Diagrams SiUS34 907 232 Appendix FXMQ07P 09P 12P 18P 24P 30P 36P 48PVJU 3D065984A...
Page 242: ...SiUS34 907 Wiring Diagrams Appendix 233 FXHQ12M 24M 36MVJU 3D048116A...
Page 243: ...Wiring Diagrams SiUS34 907 234 Appendix FXAQ07M 09M 12M 18M 24MVJU 3D046039D...
Page 244: ...SiUS34 907 Wiring Diagrams Appendix 235 FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Page 247: ...Option List SiUS34 907 238 Appendix...
Page 249: ...Example of Connection 240...
Page 263: ...Precautions for New Refrigerant R 410A SiUS34 907 254 Precautions for New Refrigerant R 410A...