21
|
Configuration
Installer and user reference guide
155
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
[2‑81]
Cooling comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings, see
"21.2 Energy saving and optimum operation"
[2‑82]
Heating comfort setting.
This setting is used in conjunction with setting [2‑9].
[2‑82]
Heating comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings, see
"21.2 Energy saving and optimum operation"
[2‑88]
Automatic leak detection activation.
When you want to use the automatic leak detection function you have to activate
this setting. By activating setting [2‑88], the automatic leak detection will be
executed depending on the defined value setting. The timing for the next
automatic refrigerant leak detection is subject to setting [2‑65]. The automatic leak
detection will be executed in [2‑65] days.
Each time when the automatic leak detection function was executed the system
will stay idle until it is restarted by manual thermo ON request or by next
scheduled action.
[2‑88]
Description
0 (default)
No leak detection planned.
1
Leak detection planned once in [2‑65] days.
2
Leak detection planned every [2‑65] days.
21.1.9 Indoor unit field setting
15(25)-13
Safety system deactivation.
When the room where the indoor unit is installed is big enough that no safety
measure is required, the R32 leak safety system in that indoor unit can be
deactivated by this setting.
Safety system deactivation
Setting
1
st
code
Function
2
nd
code
Description
15/25
13
R32 leak safety
system setting
01
Disabled
02
Enabled