Troubleshooting
Installer and user reference guide
48
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
Main code
Contents
External ventilation input error
Centralised address duplication
Malfunction in communication centralised control device - indoor
unit
Faulty wiring indoor/SV unit
Auto address malfunction (inconsistency)
Airflow rate below the legal limit (for EKEA/EKVDX)
(a)
The error code is only shown on the user interface of the indoor unit where the error
occurs.
10.2 Symptoms that are NOT system malfunctions
The following symptoms are NOT system malfunctions:
10.2.1 Symptom: The system does not operate
▪
The air conditioner does not start immediately after the ON/OFF button on the
user interface is pressed. If the operation lamp lights, the system is in normal
condition. To prevent overloading of the compressor motor, the air conditioner
starts 5 minutes after it is turned ON again in case it was turned OFF just before.
The same starting delay occurs after the operation mode selector button was
used.
▪
If "Under Centralised Control" is displayed on the user interface, pressing the
operation button causes the display to blink for a few seconds. The blinking
display indicates that the user interface cannot be used.
▪
The system does not start immediately after the power supply is turned on. Wait
one minute until the microcomputer is prepared for operation.
10.2.2 Symptom: Cool/Heat cannot be changed over
▪
When the display shows
(changeover under centralised control), it shows
that this is a slave user interface.
▪
When the cool/heat changeover remote control switch is installed and the
display shows
(changeover under centralised control), this is because cool/
heat changeover is controlled by the cool/ heat changeover remote control
switch. Ask your dealer where the remote control switch is installed.
10.2.3 Symptom: Fan operation is possible, but cooling and heating do not work
Immediately after the power is turned on. The micro computer is getting ready to
operate and is performing a communication check with all indoor units. Please wait
12 minutes maximally until this process is finished.
10.2.4 Symptom: The fan speed does not correspond to the setting
The fan speed does not change even if the fan speed adjustment button is pressed.
During heating operation, when the room temperature reaches the set
temperature, the outdoor unit goes off and the indoor unit changes to whisper fan