2
11
266
• HRV
•
VKM-GA(M)V1
• HRV
•
Heat Reclaim Ventilation
The right column of Table A shows
the duct diameter equivalent to this
pressure loss of the local feature.
Note that the values shown in the
table are for
λ
= 0.018. For other
values of the friction resistance coefficient (
λ
) to be used, use the following equation to find appropriate
conversion.
Table A
(Example)
No.
Name
Sketch
Status
Loss
coefficient
ζ
H/W
R/dR/W
1
R bend, round duct
–
0.5
0.90
0.75
0.45
1.0
0.33
1.5
0.24
2.0
0.19
2
Straight bend, round duct
–
–
1.30
3
R bend, rectangular duct
0.25
0.5
1.25
0.75
0.60
1.0
0.37
1.5
0.19
0.5
1.10
0.5
0.75
0.50
1.0
0.28
1.5
0.13
1.0
0.5
1.00
0.75
0.41
1.0
0.22
1.5
0.09
4.0
0.5
0.96
0.75
0.37
1.0
0.19
1.5
0.07
4
Straight bend, rectangular duct
0.25
–
1.25
0.5
1.47
1.0
1.50
4.0
1.38
5
Pipe inlet (with round hood)
θ
20°
0.02
40°
0.03
60°
0.05
90°
0.11
120°
0.20
6
Pipe inlet
(with rectangular hood)
θ
20°
0.13
40°
0.08
60°
0.12
90°
0.19
120°
0.27
le = d
ζ
λ
le : equivalent straight pipe length of partial resistance...[m]
d : straight pipe diameter................................................ [m]
ζ
: Local loss coefficient
d
R
d
R
H
W
H
W
V
θ
V
θ
(For galvanized steel pipe with
λ
= 0.02, approximate value)
External hood
(equivalent straight pipe length 9m)
VI
V
IV
III
I
II
5m
Duct diameter
φ
100
Material: galvanized
steel pipe
Ventilating fan intended for
use with a ducted system
0.5m
0.5m
Summary of Contents for VAM-FA8VE
Page 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Page 2: ......
Page 152: ......
Page 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Page 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...