• HRV • Heat Reclaim Ventilation
133
• HRV • VAM-FA8VE
1
9
9
Control System
9-3
Applicable patterns
9-3-4
Examples of mistakes in wiring and system designing
Setting of Remote Control for HRV unit
List of Settings
Caution
1. The setting positions are set at “01” at the factory.
The ventilation air flow, however, is set at “05” (medium) in the HRV unit. When lower or higher setting is desired, change the setting
after installation.
Group number setting for centralized control
1. Mode no. 00: Group control
2. Mode no. 30: Individual control
* Regarding the setting procedure, refer to the section “Group number setting for centralized control” in the operating manual of either
the on / off control or the central control.
Mode no.
Setting
switch
no.
Description of Setting
Setting position no. (Caution *1.)
Group
settings
Individual
settings
01
02
03
04
05
06
17
27
0
Filter cleaning time setting
Approx.
2500 hours
Approx.
1250 hours
No
counting
—
—
—
2
Precool / preheat on / off setting
Off
On
—
—
—
—
3
Precool / preheat time setting
30 min
45 min
60 min
—
—
—
4
Fan speed initial setting
Normal
Ultra high
—
—
—
5
Yes / No setting for direct duct
Connection with VRV system
No duct (Air
flow
setting)
With duct
(fan off)
—
—
—
—
Setting for cold areas
(Fan operation selection for heater
thermo OFF)
—
—
No duct
With duct
Fan off
Fan L
Fan off
Fan L
7
Centralized / individual setting
Centralized
Individual
—
—
—
—
8
Centralized zone interlock setting
No
Yes
Priority on
Operation
—
—
—
9
Preheat time extension setting
0 min
30 min
60 min
90 min
—
—
18
28
0
External signal JC / J2
Last
command
Priority on
external
input
—
—
—
—
1
Setting for direct Power ON
Off
On
—
—
—
—
2
Auto restart setting
Off
On
—
—
—
—
4
Indication of ventilation mode / Not
indication
Indication
No
Indication
—
—
—
—
7
Fresh up air supply / exhaust setting
No
Indication
No
Indication
Indication
Indication
—
—
Supply
Exhaust
Supply
Exhaust
—
—
8
External input terminal function
selection (between J1 and JC)
Fresh-up
Overall
alarm
Overall
malfunctio
n
Forced off
Fan forced
off
Air flow
Increase
9
KRP50-2 output switching selection
(between 1 and 3)
Humidify
Abnormal
Fan on / off
—
—
—
19
29
0
Ventilation air flow setting
Low
Low
Low
Low
High
High
2
Ventilation mode setting
Automatic
Exchange
By pass
—
—
—
3
“Fresh Up” on / off setting
Off
On
—
—
—
—
8
Electric heater setting
No delay
No delay
On, off
delay
On, off
delay
—
—
Summary of Contents for VAM-FA8VE
Page 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Page 2: ......
Page 152: ......
Page 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Page 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...