Product Specification
7 - 1 VKM-GAMV1
7 - 1 - 9 Installation
7 - 1 - 9 - 1 Installation method
VKM100GAMV1
3D051321
NOTES
1
Lea
v
e s
p
ace for ser
v
icing the unit and include ins
p
ection hatch. (Always o
p
en a
hole on the side of the control box so that the air filters, heat exchange elements,
fans, and humidifier elements can easily be ins
p
ected and ser
v
iced.)
2
Install the two outdoor ducts with down slo
p
e (slo
p
e of 1/30 or more) to
p
re
v
ent
entry of rain water, also,
p
ro
v
ide insulation for three ducts (outdoor ducts and
indoor su
pp
ly air duct) to
p
re
v
ent dew condensation) (material: glass wool of
2
5mm thick).
3
Do not turn the unit u
p
side down.
4
Use city water of clean water. Include water su
pp
ly
p
i
p
ing with straner, a water
su
pp
ly shut-off
v
al
v
e, and a drain
v
al
v
e (both locally
p
rocured) somewhere along
the water su
pp
ly
p
i
p
ing that can be reached from the ins
p
ection.
5
It is im
p
ossible to connect the water su
pp
ly
p
i
p
ing directly to
p
ublic
p
i
p
ing, use
a cistern tank (of the a
pp
ro
v
ed ty
p
e), if you need to get your water su
pp
ly from
p
ublic
p
i
p
ing.
6
Make sure the su
pp
ly water 0.0
2
M
P
a to 0.4
9
M
P
a (0.
2
kg/cm² to 5kg/cm²)
7
Make sure the su
pp
ly water is between 5°
C
and 40°
C
in tem
p
erature.
8
Insulate the water su
pp
ly
p
i
p
ing to
p
re
v
ent condensation from forming.
9
Make sure install drain
p
i
p
ing, and insulate drain
p
i
p
ing to
p
re
v
ent dew
condensation.
10
Kee
p
the drain
p
i
p
e short and slo
p
ing downwards at a gradient of at least 1/100
to
p
re
v
ent air from forming.
11
Install in a location where the air around the unit or taken into the humidifier will
not dro
p
below 0°
C
.
1
2
Do not use a bent ca
p
or a round hood as the outdoor hood if they might get
rained on directly (we recommend using a dee
p
hood) (o
p
tional accessory).
13
In areas where freezing may occur, always take ste
p
s to
p
re
v
ent the
p
i
p
es from
freezing.
14
Do not
p
lace something which shouldn’t be get wet at the below of this unit. The
dew would fall at following case, where humidity is 80% more, or the exit of drain
socket is choked u
p
, or the air filter is
v
ery dirty.
15
Feed clean water, the su
pp
ly water is hard water. Use water softener because
of short life. Life of humidifying element is about 3 years 4,000 hours), under the
su
pp
ly water conditions of hardness: 150mg/L. (Life of humidifying element is
about 1 year (1500 hours), under the su
pp
ly water conditions of hardness:
400mg/L.)
1
2
14
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Ins
p
ection
hatch
C
istern tank
Maintenance s
p
ace for the heat exchanger
elements the air filters, fans and humidifier
360 (In case of
450 ins
p
ection hatch)
140 (In case of
600 ins
p
ection hatch)
Ins
p
ection
hatch
Round sha
p
e food
(Locally
p
rocured)
1688
Heat insulator
(Locally
p
rocured)
Air suction grille
(Locally
p
rocured)
W
ater su
pp
ly shut-off
v
al
v
e
(Locally
p
rocured)
Flexible duct
(Locally
p
rocured)
Heat insulator
(Locally
p
rocured)
Air discharge grille
(Locally
p
rocured)
Air discharge grille
(Locally
p
rocured)
15
0~
2
50
Mo
re than 6
00
C
ontrol box
2
m~50m
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
ø2
00
Nominal diameter
(Locally
p
rocured)
Branch duct
(Locally
p
rocured)
Strainer
(Accessory)
Drain
v
al
v
e
(Locally
p
rocured)
A gradient of
more than 1/30
Refrigerant
p
i
p
ing (gas
p
i
p
e)
(
ø
1
2
.7 flare connection)
Refrigerant
p
i
p
ing (liquid
p
i
p
e)
(
ø
6.4 flare connection)
Sus
p
ension bolt
(Locally
p
rocured)
450 • 600
ins
p
ection hatch
(Locally
p
rocured)
RA
(Return air from room)
SA
(Su
pp
ly air to room)
Slo
p
ing downards at a
gradient of the 1/100
Silencer
(Locally
p
rocured)
Summary of Contents for VAM-FA8VE
Page 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Page 2: ......
Page 152: ......
Page 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Page 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...